Installation next to tanks containing one liquid and foam

• The top process connection of the bypass chamber must be above the maximum level of

liquid.

• The bottom process connection of the bypass chamber must be below the lowest measured

level of liquid.

Installation next to tanks containing more than one liquid

• The top process connection of the bypass chamber must be above the maximum level of

liquid.

• The bottom process connection of the bypass chamber must be below the lowest measured

level of liquid.

• Additional process connections are necessary for the liquids to circulate freely along the

length of the bypass chamber. These additional process connections must be separated by a
distance equal to or less than the minimum level of the bottom liquid.

Figure 3-10: Installation recommendations for bypass chambers that contain more than one liquid

1 Bypass chamber
2 Distance between connections ≤ the minimum level of the bottom liquid.
3 Additional process connection