7.8 Sensor response times

Thermometer response times are generally indicated as "50% time" (t

05

) and "90% time" (t

09

).

"50% time" refers to the time needed for a thermometer signal to achieve 50% of its end value in
the face of erratic temperature changes (this applies analogously to "90% time").

Thermometer with welded, straight thermowell

Thermometer without thermowell (TRA/TCA-S34 and -S50 with Ø 6 mm / 0.24")

INFORMATION!
You can find more information about response times in VDI 3522.

Ø of thermowell

Pt100 RTD

Thermocouple

[mm]

["]

t

05

[s]

t

09

[s]

t

05

[s]

t

09

[s]

9

0.35

17

52

14

42

11

0.43

21

58

17

46

12

0.47

22

66

18

54

Water flows against the thermometer at 0.4 m/s or 1.31 ft/s

Sensor

Water with 0.4 m/s or 1.31 ft/s

Air with 1 m/s or 3.28 ft/s

t

05

[s]

t

09

[s]

t

05

[s]

t

09

[s]

Pt100 RTD

3.5

8

24

54

Thermocouple

2.5

7

21

50