Electrical connections
Power supply
Only necessary when using a temperature transmitter and depends
on transmitter type (typically 24 VDC).
Power consumption
Only when using a temperature transmitter (typically 550 mW).
Cable entry (connection head)
Depends on the thread to connect to the neck tube:
•
For thread according to DIN: M20 x 1.5
•
For thread according to ASME/ANSI: ½" NPT, no cable gland
supplied here.
Current output
Current output
Current output
Current output
Output range
Exists only when using a temperature transmitter and depends on
transmitter type (typically 4...20 mA, HART
®
, Profibus-PA).
Error signal
According to NAMUR NE 43, selectable: upper value ≥ 21.0 mA, lower
value ≤ 3.6 mA, the factory default is the upper value.
Load
Relevant only when using a temperature transmitter and then
dependent on transmitter type (typically 250 Ω).
Other electrical characteristics
Other electrical characteristics
Other electrical characteristics
Other electrical characteristics
Galvanic isolation
Relevant only when using a temperature transmitter (see transmitter
handbook).
Time constant
More detailed information can be found in the subsection "Response
times" of the section "Technical data".
Approvals and certificates
Electromagnetic compatibility
See handbook for temperature transmitter used.
ATEX
Ex i pending for all thermometers with a measuring insert featuring a
diameter of 6 mm / 0.24" and the following sensor:
1 x Pt100, class A, wire-wound RTD.
Functional safety
SIL2 with temperature transmitter TT51 C/R