7

TECHNICAL DATA

64

OPTITEMP TRA/TCA PLUS

www.krohne.com

01/2012 - 4000630301 - MA OPTITEMP TRA/TCA Plus R01

7.4 Measuring accuracy

The measuring accuracy depends largely on the following factors:

• The version of the measuring insert (type of sensor, type of circuit, measuring range).
• The correct dimensions (diameter, wall thickness) and insertion length of the thermowell for

good thermal coupling to the process temperature (insufficient insertion depth often results
in measurement errors).

• The type of temperature transmitter used.

With the exception of the TT 60 C/R version, all of the temperature transmitters generate an
analogue output signal. For this reason, the following table indicates the measuring accuracy of
most of the transmitters as a percentage of the measuring range:

Temperature transmitter

INFORMATION!
Please consult the appropriate handbook for further information regarding the accuracy of the
measuring inserts and the temperature transmitters.

Type of temperature transmitter

Accuracy (% of the measuring range or °K)

TT 10 C/R (analogue, standard, 4...20 mA)

±

0.15%

TT 11 C/R (analogue, 3- or 4-wire circuit:

0...10 VDC)

±

0.15%

TT 20 C/R (analogue, 4...20 mA)

±

0.10%

TT 30 C/R (digital, 4...20 mA, standard)

±

0.10%

TT 31 R (3-wire-circuit, 4...20 mA

±

0.10%

TT 32 R (4-wire circuit, 0/4...20 mA: 0/2...10 VDC)

±

0.20%

TT 40 C/R (digital, 4...20 mA, precise)

±

0.05%

TT 50 C/R (digital, 4...20 mA, HART

®

)

±

0.10%

TT 51 C/R (digital, 4...20 mA, HART

®

, SIL2)

±

0.05%

TT 60 C/R (digital, Profibus-PA)

±

0.10°K