INSTALLATION

1

7

OPTISONIC 6300

www.krohne.com

07/2009 - 7.30959.24.00 - QS OPTISONIC 6300 R04 en

1.7.1 Inlet, outlet and recommended mounting area

1.7.2 Long horizontal pipes

• Install on slightly ascending pipe section.
• If not possible, ensure adequate velocity to prevent air, gas or vapor from collecting in upper

part.

• In partially filled pipes, the clamp-on flowmeter will report incorrect flow rates, or not

measure.

Figure 1-3: Inlet, outlet and recommended mounting area

1 Min. 10 DN
2 Min. 5 DN
3 OK, 120°

CAUTION!

Especially for XT (eXtended Temperature) versions:

Always install the sensor at a non-insulated part of the pipe. Remove any insulation if
necessary!

Bend radius of cable plus connection box needs 10 cm / 4" additional non insulated pipe
section.

Always wear protections gloves.

Figure 1-4: Long horizontal pipes