ELECTRICAL CONNECTIONS

2

23

OPTISONIC 6300

www.krohne.com

07/2009 - 7.30959.24.00 - QS OPTISONIC 6300 R04 en

100…230 VAC (-15% / +10%)

• Connect the protective ground conductor PE of the mains power supply to the separate

terminal in the terminal compartment of the signal converter.

• Connect the live conductor to the L terminal and the neutral conductor to the N terminal.

24 VAC/DC (-15% / +10%)

• For reasons to do with the measurement process, connect a functional ground FE to the

separate U-clamp terminal in the terminal compartment of the signal converter.

• When connecting to functional extra-low voltages, provide a facility for protective separation

(PELV) (VDE 0100 / VDE 0106 and/or IEC 364 / IEC 536 or relevant national regulations).

Figure 2-7: Construction (field version)

1 Cover, electronics compartment
2 Cover, terminal compartment for power supply and inputs/outputs
3 Cable entry for power
4 Cable entry for inputs/outputs
5 Cable entry for sensor cable
6 Cover, sensor terminal compartment