Technical data – KROHNE OPTISONIC 6300 Quickstart EN User Manual
Page 50
4
TECHNICAL DATA
50
OPTISONIC 6300
www.krohne.com
07/2009 - 7.30959.24.00 - QS OPTISONIC 6300 R04 en
Status output / limit switch
Status output / limit switch
Status output / limit switch
Status output / limit switch
Function and settings
Settable as automatic measuring range change, indicator for
direction of flow, overflow, error, operating point or empty pipe
detection
Valve control with activated dosing function
Status and/or control: ON or OFF
Operating data
Basic I/Os
Basic I/Os
Basic I/Os
Basic I/Os
Modular I/Os
Modular I/Os
Modular I/Os
Modular I/Os
Ex-i
Ex-i
Ex-i
Ex-i
Active
-
U
int
= 24 VDC
I ≤ 20 mA
open: I ≤ 0.05 mA
closed:
U
0, nom
= 24 V at
I = 20 mA
-
Passive
U
ext
≤ 32 VDC
I ≤ 100 mA
open:
I ≤ 0.05 mA at
U
ext
= 32 VDC
closed:
U
0, max
= 0.2 V at
I ≤ 10 mA
U
0, max
= 2 V at
I ≤ 100 mA
U
ext
= 32 VDC
I ≤ 100 mA
R
L, max
= 47 kΩ
open:
I ≤ 0.05 mA at
U
ext
= 32 VDC
closed:
U
0, max
= 0.2 V at
I ≤ 10 mA
U
0, max
= 2 V at
I ≤ 100 mA
-
NAMUR
-
Passive to
EN 60947-5-6
open: I
nom
= 0.6 mA
closed: I
nom
= 3.8 mA
Passive to
EN 60947-5-6
open: I
nom
= 0.43 mA
closed: I
nom
= 4.5 mA
U
I
= 30 V
I
I
= 100 mA
P
I
= 1 W
C
I
=10 nF
L
I
= 0 mH