P/N 3100179 ISSUE 1

PAGE 2

1.3 Object Interfaces:

OBJECT

Effect on Behavior

Identity (1)

Message router

Message Router (2)

Explicit message connection instance

Devicenet (3)

Message router

Assembly (4)

I/O connection or message router

Connection (5)

Message router

1.4 Identification of I/O Assembly Interfaces:

Instance Number

Type

Name

1

Input/Output

LEDs ON/OFF, LED diagnostics, and sounder control

1.5 Format of I/O Assembly data Attribute:

Input to the DeviceNet bus as a response to the poll command from master node.

Data Byte 0 value indicates the LEDs are OK or are burned out.
Data Byte 1 value indicates the LEDs were on or off when last poll command was received.
Data Byte 2 value indicates the current sounder module control value.

BYTE

BIT7

BIT6

BIT5

BIT4

BIT3

BIT2

BIT1

BIT0

0

DON'T

DON'T

DON'T

DON'T

DON'T

LED 3

LED 2

LED 1

CARE

CARE

CARE

CARE

CARE

1 = REP

1 = REP

1 = REP

0 = OK

0 = OK

0 = OK

1

DON'T

DON'T

DON'T

DON'T

DON'T

LED 3

LED 2

LED 1

CARE

CARE

CARE

CARE

CARE

1 = ON

1 = ON

1 = ON

0 = OFF

0 = OFF

0 = OFF

2

0

0

0

0

Sounder

Tone

Tone

Tone

1 = ON

MSB

LSB

0 = OFF