17.2. Conventional Building
Conventional houses have different ventilation needs than do tunnel ventilated houses.
In the example below our house will be set up as follows:
H1
H2
H3
H4
H5
F6
F1
F2
F3
F4
F5
F7
F8
F9
F10
F11
F12
S1
S2
S3
S4
Stage
Mode
Equipment
Sensors
Offset
Diff
On Timer
1
Heat
H-1,2,3
1,2
3
1
---
2
Heat
H-4,5
3
3
1
---
3
Cool-Neg
F-2,5
1,2
1
1
Yes
4
Cool-Neg
F-1,3
3
3
1
Yes
5
Cool-Neg
F-4,6
1,2,3
3
1
No
6
Cool Stir
F-7,8,9
1,2,3
6
1
No
7
Cool Stir
F-10,11,12
1,2,3
6
1
No
8
Lighting
Lights
--
--
--
--
1.
Variable Timer
A.
Hi Temp................................................................ 70
B.
Hi Percent ............................................................. 60
C.
Lo Temp ............................................................... 40
D.
Lo Percent............................................................. 20
2.
Ramp Function .............................................................. Yes
A.
Number Of Days ................................................... 30
B.
Ending Temperature ............................................. 72
3.
Setup System ................................................................. Yes
A.
Sensors For Display .............................................. 1,2,3
B.
Unit Sensor(s) ....................................................... 1,2,3
C.
Auto Kill Fans ...................................................... Yes
D.
Power Unit............................................................ On
4.
Program Stages.............................................................. Yes
A.
Program Stage 1.................................................... Yes
1.
Mode .......................................................... Heat
2.
Stage 1 Sensors........................................... 1,2
3.
Stage 1 Offset ............................................. 3
4.
Stage 1 Differential..................................... 1
B.
Program Stage 2.................................................... Yes
1.
Mode .......................................................... Heat
2.
Stage 2 Sensors........................................... 3
3.
Stage 2 Offset ............................................. 3
4.
Stage 2 Differential..................................... 1
C.
Program Stage 3.................................................... Yes
1.
Mode .......................................................... Cool-Neg
2.
Stage 3 Sensors........................................... 1,2,3
3.
Stage 3 Offset ............................................. 1