Changing the temperature shutdown level – Brocade FastIron GS and GS-STK Hardware Installation Guide User Manual
Page 95

Brocade FastIron GS and GS-STK Hardware Installation Guide
85
53-1002186-02
Managing temperature settings
7
DRAFT: BROCADE CONFIDENTIAL
Changing the temperature warning and shutdown levels
The default warning temperature is 45.0 C degrees. You can change the warning temperature
using the following command. The valid range is 0 – 125 C degrees.
To change the temperature at which the device sends a warning, enter a command such as the
following at the Privileged EXEC level of the CLI:
FastIron# temperature warning 47
Syntax: temperature warning <value>
The <value> can be 0 – 125.
For IronStack devices
To change the temperature warning level for an FGS-STK device in an IronStack, enter a command
similar to the following:
FGS624 Switch# temperature warning 2 82
Syntax: temperature warning <unit-id> <value>
Changing the temperature shutdown level
To change the temperature at which the device sends a warning, enter a command similar to the
following:
FastIron#temperature shutdown 47
Syntax: temperature shutdown <value>
The <value> can be 0 – 125.
For IronStack devices
To change the temperature shutdown level for an FGS-STK device in an IronStack, enter a
command similar to the following:
FGS624 Switch#temperature shutdown 2 90
Syntax: temperature shutdown <unit-id> <value>
FastIron#show log
Syslog logging: enabled (0 messages dropped, 0 flushes, 0 overruns)
Buffer logging: level ACDMEINW, 8 messages logged
level code: A=alert C=critical D=debugging M=emergency E=error
I=informational N=notification W=warning
Static Log Buffer:
Dynamic Log Buffer (50 entries):
at 0 days 0 hours 2 minutes 0 seconds, level alert
Temperature 48.0 C degrees, warning level 45.0 C degrees
at 0 days 0 hours 1 minutes 0 seconds, level alert
Temperature 50.0 C degrees, warning level 45.0 C degrees