beautypg.com

Device status, Device status -1, 7 . device status – Yokogawa EJA115 User Manual

Page 34

background image

IM 01C22T02-01E

7-1

7. DEVICE STATUS

7 .

DEVICE STATUS

Device setting status and failures of EJA are indicated by using parameter DEVICE_STATUS_1,
DEVICE_STATUS_2 and DEVICE_STATUS_3 (index 1045, 1046 and 1047) in Resource Block.

Table 7.1 Contents of DEVICE_STATUS_1 (index 1045)

Display

through DD

Description

Hexadecimal

Sim.enable
Jmpr On

RB in O/S mode
(AL.21)

AMP Module
Failure 2 (AL.03)

LINK OBJ. 1/17
not open

LINK OBJ. 2
not open

LINK OBJ. 3
not open

LINK OBJ. 4
not open

LINK OBJ. 5
not open

LINK OBJ. 6
not open

LINK OBJ. 7
not open

LINK OBJ. 8
not open

LINK OBJ. 9
not open

LINK OBJ. 10
not open

LINK OBJ. 11
not open

LINK OBJ. 12
not open

LINK OBJ. 13
not open

LINK OBJ. 14
not open

LINK OBJ. 15
not open

LINK OBJ. 16
not open

SIMULATE_ENABLE switch
is ON.

Resource Block is in O/S
mode.

AMP module failure

Link object 1 is not open.

Link object 2 is not open.

Link object 3 is not open.

Link object 4 is not open.

Link object 5 is not open.

Link object 6 is not open.

Link object 7 is not open.

Link object 8 is not open.

Link object 9 is not open.

Link object 10 is not open.

Link object 11 is not open.

Not used for EJA.

Not used for EJA.

Not used for EJA.

Not used for EJA.

Not used for EJA.

0x80000000

0x40000000

0x20000000

0x10000000

0x08000000

0x04000000

0x02000000

0x01000000

0x00800000

0x00400000

0x00200000

0x00100000

0x00080000

0x00040000

0x00020000

0x00010000

0x00008000

0x00004000

0x00002000

0x00001000

0x00000800

0x00000400

0x00000200

0x00000100

0x00000080

0x00000040

0x00000020

0x00000010

0x00000008

0x00000004

0x00000002

0x00000001

T0701.EPS

Table 7.2 Contents of DEVICE_STATUS_2 (index 1046)

Display

through DD

Description

Hexadecimal

Data is out of
LCD display
range (AL.61)

Zero Adjust value
is out of normal
range (AL.64)

Temperalure is
out of normal
range (AL.43)

Static Pressure is
out of normal
range (AL.42)

Differential
Pressure is out of
normal range
(AL.41)

AMP Module
Failure 3 (AL.02)

AMP Module
Failure 2 (AL.03)

AMP Module
Failure 1 (AL.02)

Capsule Module
Failure 3 (AL.01)

Capsule Module
Failure 2 (AL.01)

Capsule Module
Failure 1 (AL.01)

Data is out of LCD display
range.

Zero adjustment value is out
of range.
Alarm is generated when the
value is out of LRL -10% to
URL +10%.

Process temperature is out
of limit.
Alarm is generated when the
temperature is out of -50 to
130 degC.

Static pressure is out of
MWP.
Alarm is generated when the
static pressure exceeds
110% of MWP.

Differential pressure is out of
range.
Alarm is generated when the
value is out of LRL -10% to
URL +10%.

Amp module failure

Amp module failure

Amp module failure

Capsule module failure

Capsule module failure

Capsule module failure

0x80000000

0x40000000

0x20000000

0x10000000

0x08000000

0x04000000

0x02000000

0x01000000

0x00800000

0x00400000

0x00200000

0x00100000

0x00080000

0x00040000

0x00020000

0x00010000

0x00008000

0x00004000

0x00002000

0x00001000


0x00000800

0x00000400


0x00000200


0x00000100

0x00000080

0x00000040

0x00000020

0x00000010

0x00000008

0x00000004

0x00000002

0x00000001

T0702.EPS

This manual is related to the following products: