2 function block execution control, 6 block setting, 1 link object – Yokogawa EJA115 User Manual
Page 27: Function block execution control -5, Block setting -5, Link object -5, Set the parameter for function block vfd, Set link objects as shown in table 5.7
IM 01C22T02-01E
5-5
5. CONFIGURATION
T0504-2.EPS
13
FasDllSubscriber
SynchronizationDlcep
Not used for EJA.
14
FmsVfdId
Sets VFD for EJA to be
used.
0x1: System/network
management VFD
0x1234: Function block
VFD
15
FmsMaxOutstanding
ServiceCalling
Set 0 to Server. It is not
used for other applications.
16
FmsMaxOutstanding
ServiceCalled
Set 1 to Server. It is not
used for other applications.
17
FmsFeatures
Supported
Indicates the type of
services in the application
layer. In the EJA, it is
automatically set according
to specific applications.
Sub-
index
Parameter
Description
12
FasDllSubsriberTime
WindowSize
Not used for EJA.
17 VCRs are factory-set as shown in the table below.
Table 5.5
VCR List
T0505.EPS
Index
(SM)
VCR
Number
Factory Setting
293
For system management (Fixed)
1
294
Server (LocalAddr = 0xF3)
2
295
Server (LocalAddr = 0xF4)
3
296
Server (LocalAddr = 0xF7)
4
297
Trend Source (LocalAddr = 0x07,
Remote Address=0x111)
5
298
Publisher for AI1 (LocalAddr = 0x20)
6
299
Alert Source (LocalAddr = 0x07,
Remote Address=0x110)
7
300
Server (LocalAddr = 0xF9)
8
301
Publisher for AI2 (LocalAddr = 0x21)
9
302
Not used.
10
303
Not used.
11
304
Not used.
12
305
Not used.
13
306
Not used.
14
307
Not used.
15
308
Not used.
16
309
Not used.
17
5.5.2 Function Block Execution Control
According to the instructions given in Section 5.3, set
the execution cycle of the function blocks and schedule
of execution.
5.6 Block Setting
Set the parameter for function block VFD.
5.6.1 Link Object
A link object combines the data voluntarily sent by the
function block with the VCR. The EJA has eleven link
objects. A single link object specifies one combination.
Each link object has the parameters listed in Table 5.6.
Parameters must be changed together for each VCR
because the modifications made to each parameter may
cause inconsistent operation.
Table 5.6
Link Object Parameters
T0506.EPS
Sub-
index
Parameters
Description
1
LocalIndex
Sets the index of function
block parameters to be
combined; set “0” for Trend
and Alert.
2
VcrNumber
Sets the index of VCR to
be combined. If set to “0”,
this link object is not used.
3
RemoteIndex
Not used in EJA. Set to “0”.
5
StaleCountLimit
Set the maximum number
of consecutive stale input
values which may be
received before the input
status is set to BAD. To
avoid the unnecessary
mode transition caused
when the data is not
correctly received by
subscriber, set this
parameter to “2” or more.
4
ServiceOperation
Set one of the following.
Set only one each for link
object for Alert or Trend.
0: Undefined
2: Publisher
3: Subscriber
6: Alert
7: Trend
Set link objects as shown in Table 5.7.
Table 5.7
Factory-Settings of Link Objects (example)
T0507.EPS
Index
Link Object #
Factory Settings
30000
AI1.OUT
→
VCR#6
1
30001
Trend
→
VCR#5
2
30002
Alert
→
VCR#7
3
30003
AI2.OUT
→
VCR#9
4
30004
Not used
5
30005
Not used
6
30006
Not used
7
30007
Not used
8
30008
Not used
9
30009
Not used
10
30010
Not used
11