Proface AGP3500 - 10.4 DIO HMI" User Manual
Page 8
8
DC24 V Interface
y To avoid an electric shock, prior to connecting the GP unit’s power cord terminals to
the power terminal block, confirm that the GP unit’s power supply is completely
turned OFF, via a breaker, or similar unit.
y Supplying a power voltage other than that specified will damage the power source
and the GP unit.
y Since there is no power switch on the GP unit, be sure to attach a breaker switch to
the power cord.
y When the FG terminal is connected, be sure the wire is grounded.
• Be sure to twist Power Input wires from a part close to the power supply.
• It's recommended to use the provided common mode filter on the direct-connect cable to
reduce noise.
Power Supply Cautions
• Input and Output signal lines must be separated from the power control cables for operational
circuits.
• To improve the noise resistance, be sure to twist the ends of the power cord wires before
connecting them to the power supply.
• The GP unit’s power supply cord should not be bundled with or kept close to main circuit
lines (high voltage, high current), or input/output signal lines.
• To reduce noise, make the power cord as short as possible.
• If the supplied voltage exceeds the GP unit’s range, connect a voltage transformer.
• Between the line and the ground, be sure to use a low noise power supply. If there is an excess
amount of noise, connect a noise reducing transformer.
• The temperature rating of field installed conductors: 60
°C only.
• DC 24V input unit must be used with a Class 2 power supply.
Cable Color
Signal Name
Direction
Description
Red
DC24 V
Input
Power Input DC24 V
Black
0 V
Input
Power Input 0 V
Green
FG
*1
*1 Select AWG16 cable to use out of two green cables.
⎯
Frame Ground (Common with SG)
External
power supply
24 VDC
GP
24 VDC
Common
field filter
3
0 V
24 VDC
0 V
4
1
2
FG
FG
■ The black square indicates the connection point
for the dedicated cable and common field filter.
- AGP3400 - 7.5 DIO HMI" AGP3300 - 5.7 DIO HMI" AGP3600 - 12.1 FLEX Network HMIs" AGP3500 - 10.4 FLEX Network HMI" AGP3400 - 7.5 FLEX Network HMI" AGP3600 - 12.1 CANopen HMI" AGP3500 - 10.4 CANopen HMI" AGP3400 - 7.5 CANOpen HMI" AGP3300 - 5.7 CANopen HMI" AGP3300H - 5.7 Handheld HMIs" AGP3750 - 15 Multi-Media HMI" AGP3650 - 12.1 Multi-Media HMIs" AGP3550 - 10.4 Multi-Media HMIs" AGP3450 - 7.5 Multi-Media HMI" AGP3360 - 5.7 Multi-Media HMI" AST3300 - 5.7 Basic HMI" AST3200 - 3.8 Basic HMI" AGP3600 - 12.1 Standard HMIs" AGP3500 - 10.4 Standard HMIs" AGP3400 - 7.5 Standard HMI" AGP3300 - 5.7 Standard HMI" AGP3200 - 3.8 Standard HMI"