Proface AGP3500 - 10.4 DIO HMI" User Manual
Page 11
![background image](/manuals/358908/11/background.png)
11
For GP units with emergency switches, the enabled emergency switch activates the contact
output. To reset the emergency stop status (lock status), pull the button forward, or turn the
button in the direction indicated by arrow.
When the emergency switch is pressed, ON/OFF status of the EMG0 to EMG2 signals are as
follows:
( ) indicates contact status.
• These signal lines must be disconnected (NC) when a GP unit without an emergency switch is
used.
Key Switch Output Interface
• Turning OFF GP unit with the key switch
Emergency Stop Reset
Emergency Stop
EMG0
0 (OFF)
1 (ON)
EMG1
1 (ON)
0 (OFF)
EMG2
1 (ON)
0 (OFF)
Cable Color/
Marking Color,
Number
Signal Name
Meaning
Orange/None
KEY_NC
Key Switch b-contact (normally closed)
Rating: DC24V, 300 mA
Orange/Black 1
KEY_NO
Key Switch a-contact (normally open)
Rating: DC24V, 300 mA
EMG2A
EMG1A
EMG0A
EMG0B
EMG1B
EMG2B
DC24V
GP
OFF
ON
KEY_NO
KEY_NC
GP3000H Cable
- AGP3400 - 7.5 DIO HMI" AGP3300 - 5.7 DIO HMI" AGP3600 - 12.1 FLEX Network HMIs" AGP3500 - 10.4 FLEX Network HMI" AGP3400 - 7.5 FLEX Network HMI" AGP3600 - 12.1 CANopen HMI" AGP3500 - 10.4 CANopen HMI" AGP3400 - 7.5 CANOpen HMI" AGP3300 - 5.7 CANopen HMI" AGP3300H - 5.7 Handheld HMIs" AGP3750 - 15 Multi-Media HMI" AGP3650 - 12.1 Multi-Media HMIs" AGP3550 - 10.4 Multi-Media HMIs" AGP3450 - 7.5 Multi-Media HMI" AGP3360 - 5.7 Multi-Media HMI" AST3300 - 5.7 Basic HMI" AST3200 - 3.8 Basic HMI" AGP3600 - 12.1 Standard HMIs" AGP3500 - 10.4 Standard HMIs" AGP3400 - 7.5 Standard HMI" AGP3300 - 5.7 Standard HMI" AGP3200 - 3.8 Standard HMI"