REV 2 IRM-5000P USER’S MANUAL
15
c. The following screen will be displayed:
1. 1 Min
Press the
[1]
key to select the 1 minute test duration. Continue to step d.
2. 10 Min
Press the
[2]
key to select the 10 minute test duration. Continue to step d.
3. 30 Min
Press the
[3]
key to select the 30 minute test duration. Continue to step d.
4. Custom
Press the
[4]
key to enter a custom test duration in minutes. The following
screen will be displayed:
Type the desired test duration in minutes using the numeric keypad, and then
press the
[ENTER]
key. Continue to step d.
d. The following screen will be displayed:
1. 500V
Press the
[1]
key to select 500V for the test voltage. Continue to step e.
2. 1000V
Press the
[2]
key to select 1000V for the test voltage. Continue to step e.
3. 2500V
Press the
[3]
key to select 2500V for the test voltage. Continue to step e.
4. 5000V
Press the
[4]
key to select 5000V for the test voltage. Continue to step e.
Test Time (Minutes):
0 Minutes
TERMINAL VTG: 1 V
1. 500V 2. 1000V
3. 2500V 4. 5000V
5. Custom
TERMINAL VTG: 1 V
1. 1 Min 2. 10 Min
3. 30 Min 4. Custom
TERMINAL VTG: 1 V