REV 2 IRM-5000P USER’S MANUAL

15

c. The following screen will be displayed:

1. 1 Min

Press the

[1]

key to select the 1 minute test duration. Continue to step d.

2. 10 Min

Press the

[2]

key to select the 10 minute test duration. Continue to step d.

3. 30 Min

Press the

[3]

key to select the 30 minute test duration. Continue to step d.

4. Custom

Press the

[4]

key to enter a custom test duration in minutes. The following

screen will be displayed:

Type the desired test duration in minutes using the numeric keypad, and then
press the

[ENTER]

key. Continue to step d.

d. The following screen will be displayed:

1. 500V

Press the

[1]

key to select 500V for the test voltage. Continue to step e.

2. 1000V

Press the

[2]

key to select 1000V for the test voltage. Continue to step e.

3. 2500V

Press the

[3]

key to select 2500V for the test voltage. Continue to step e.

4. 5000V

Press the

[4]

key to select 5000V for the test voltage. Continue to step e.

Test Time (Minutes):
0 Minutes

TERMINAL VTG: 1 V

1. 500V 2. 1000V
3. 2500V 4. 5000V
5. Custom
TERMINAL VTG: 1 V

1. 1 Min 2. 10 Min
3. 30 Min 4. Custom

TERMINAL VTG: 1 V