REV 2 IRM-5000P USER’S MANUAL

11

3.0 OPERATING

PROCEDURES

3.1 Performing

Tests

3.1.1. Entering Test Record Header Information

You can enter the test record header information before performing tests. The record header
includes identifying information such as company, location, test description, etc. Once the
header information has been entered, it will apply to all subsequent test records. To enter the
header information:

a. When the unit is turned on, you will be presented with the “START-UP” menu:

NOTES

• If the IRM-5000P is running on battery power, the battery icon will be

displayed on the LCD screen as shown above. The icon also represents the
charge level of the battery.

If the IRM-5000P is plugged in, a plug icon will be displayed on the LCD
screen as shown below:

• The test terminal voltage is displayed at the bottom of the LCD screen. The

IRM-5000P can be used as a voltmeter by connecting the positive and
negative leads to a voltage source. The voltage measurement range is
from 50-1250 V(AC/DC).

Press the [2] key (UTILITIES).

b. The following screen will be displayed:

Press the

[3]

key (SETUP).

1.PRINT 2.SAVE/RES
3.SETUP

TERMINAL VTG: 1 V

1.

RUN TEST 05/05/10

2.

UTILITIES 10:10:15

Bat:

TERMINAL VTG: 1 V

1.

RUN TEST 05/05/10

2.

UTILITIES 10:10:15

Bat:

TERMINAL VTG: 1 V