Vanguard CT-7000 S2 User Manual
Page 30
CT-7000 S2 USER’S MANUAL
REV 2
25
e. The following screen will be displayed:
1. PERCENT OF STROKE
Press the
[1]
key (PERCENT OF STROKE) to set the open analysis point #2 as a
percentage of the total stroke value. The following screen will be displayed:
Type the percentage value using the numeric keypad and then press the
[ENTER]
key. The analysis points will be set and you will be returned to the “START-UP”
menu.
2. DIST FROM CLOSE
Press the
[2]
key (DIST FROM CLOSE) to set the open analysis point #2 as a distance
from the contact’s close position. The following screen will be displayed:
Type the distance value using the numeric keypad and then press the
[ENTER]
key.
The analysis points will be set and you will be returned to the “START-UP” menu.
3. CONTACT +/- TIME
Press the
[3]
key to select the CONTACT +/- TIME option. The following screen will
be displayed:
1. CONTACT PLUS TIME
Press the
[1]
key to select the CONTACT PLUS TIME option.
NOTE
For the contact plus time, the user enters the time (in milliseconds)
after the contact channel #1 made the transition from OPEN to CLOSE
or CLOSE to OPEN to define the analysis point #2.
OPEN ANALYSIS PT 2
1. CONTACT PLUS TIME
2. CONTACT MINUS TIME
OPEN ANALYSIS PT 2
DISTANCE FROM CLOSE
VALUE: 127.0 mm
“ENTER” TO CONFIRM
OPEN ANALYSIS PT 2
% OF TOTAL STROKE
VALUE: 00%
“ENTER” TO CONFIRM
OPEN ANALYSIS PT 2
1. PERCENT OF STROKE
2. DIST FROM CLOSE
3. CONTACT +/- TIME