beautypg.com

Vanguard CT-7000 S2 User Manual

Page 11

background image

REV 2 CT-7000 S2 USER’S MANUAL

6

Table 2. Functional Descriptions of CT-7000 S2 Controls and Indicators

Item

Number

Panel Markings

Functional Description

1

C1-C12

Female connectors for the contact channels. The CT-7000-12 S2 is pictured
with 12 channels.

2

0-300V

V1

3-pin connector. V1 voltage input channel is dedicated to monitoring circuit
breaker DC power supply or coil voltages. Voltage sensing range is from 0-255
volts, dc or peak ac.

3

0-300V

V2

3-pin connector. V2 voltage input channel is dedicated to detecting voltage
on/off status (present or absent) of an A/B switch. Voltage input ranges from
0-300 volts, dc or peak ac.

4

0-300V

TRIGGER

3-pin connector. Triggers voltage input for external trigger application. Voltage
levels ranging from 30 to 300 V, dc or peak ac.

5

100-120 Vac, 8A,

50-60Hz

Power plug and power switch. Built-in 12 Ampere circuit breaker.

6

GROUND

Safety ground terminal.

7, 8, 9

D1, D2, D3

TRANSDUCER

INPUT

16-pin connectors. Digital travel transducer input channels.

10

R1

5-pin connector. Resistor type transducer input. (Optional)

11

INITIATE

4-pin connector used for the switching circuit for operating the circuit breaker
under test.

12

OPEN

250V,

5A SLOW-BLOW

Open circuit fuse: 5 Ampere, 250V, SLOW-BLOW.

13

CLOSE

250V,

5A SLOW-BLOW

Close circuit fuse: 5 Ampere, 250V, SLOW-BLOW.

14

Built-in 4.5-inch wide thermal printer.

15

“PUSH” TO ARM

Spring-loaded pushbutton switch. Press and hold to complete the Trip or Close
circuits for breaker tests.

16

Rugged alpha-numeric membrane keypad.

17

Back-lit LCD screen (20 characters by 4 lines); viewable in bright sunlight and
low-light levels.

18

RS-232C

RS-232C serial computer interface port.

19

USB

USB computer interface port.