Blocking error codes – HTP ELP-199 User Manual
Page 71
71
LP-294 REV. 2.20.14
A13
State error
19
Internal software error
Exchange BCU.
A14
Rom error
20
Internal software error
A14
Rom error C
21
Internal software error
A15
Air sw not open
22
Air pressure switch not working
Check air switch, hose to air switch
(water), and wiring to BCU. Check
Menu settings.
A16
15MS XRL error
23
3 timing errors
Reset.
A17
Air sw not closed
24
Air pressure switch not working
Check air switch, hose to air switch
(water), and wiring to BCU. Check
Menu settings.
A18
Max Temp. Error
25
External overheat protection is
activated
Check overheat sensor, wiring, supply
settings, and supply controller settings.
A19
Stack error
26
Internal software error
Exchange BCU.
A20
Flame out too late
27
Flame still present 10 sec. after
closing the gas valve
Check position of ionization pin, clean
surface of ionization pin, Check the gas
valve tightness.
A21
False Flame
28
Flame is detected before ignition
Check the gas connection and gas
valve. Check position of ionization pin.
Reset. If error is not corrected,
exchange BCU.
A22
20MS XRL error
29
Internal software error
Reset the boiler.
A23
41MS XRL error
30
Internal software error
A24
Too many flame failures
31
Ten times flame loss during one
demand
Check the gas connection. Check
ionization wiring, pin, and position.
Check gas pressure.
A25
Flow switch not closed
32
Flow switch not working / No flow
Check the flow switch.
A26
Flow switch not open
33
Flow switch not working / No flow
A27
Flag byte integrity
34
Internal software error
Exchange BCU.
A28
AD Hi cpl.
35
Internal software error
A29
AD Lo cpl.
36
Internal software error
A30
Register error
37
Internal software error
A30
CPSM Error
37
Internal software error
Table 42
– Lockout Error Codes
2. BLOCKING ERROR CODES
DISPLAY
CODE
ERROR
INT.
CODE
DESCRIPTION
POSSIBLE SOLUTION
E31
REFHI TOO LO
50
Internal hardware error
Check Field Connection Board on
shortcuts, otherwise exchange BCU.
E32
REFHI TOO HI
51
E33
REFLO TOO LO
52
E34
REFLO TOO HI
53
E35
FALSE FLAME
54
Flame is detected in a state in which
no flame is allowed to be seen
Check the gas connection and gas valve.
Check position of ionization pin. Reset. If
error is not corrected, exchange BCU.
E36
WATER LEVEL DETECT
55
Low water level detected
Check the water pressure and sensor.
(N/A)
E36
WATER LEVEL MEAS
56
Low water level measurement error
E36
LOW WATER CUTOFF
57
Low water sensor error
E37
LOW WATER PRESSURE
58
Low water pressure error
E38
WATER PRESSURE
SENSOR
59
Low water pressure depending on
BCU settings
Check the water pressure and sensor.
(N/A). Check menu setting.
E39
FLUE GAS ERROR
60
Flue gas temperature error
Check the flue switch or sensor. Check
wiring. Check heat exchanger.
E41
BLOCKED DRAIN
62
Blocked drain switch is active
Check and clean condensate trap and
condensate piping.
E43
WD FREQ ERROR
64
Not a correct frequency signal or no
communication with the WD
Check the supply voltage and frequency.
Exchange BCU.
E44
PHASE ERROR
65
Hot neutral reversed
Line not connected correctly.
E45
NET FREQ ERROR
66
Net frequency error detected.
Check the supply voltage and frequency.
Exchange BCU.
E46
FAULTY EARTH ERROR
67
Faulty earth connection
Check the earth connections of the boiler
and BCU.
E47
WD COMM ERROR
68
Watchdog communication error
Exchange the BCU.
E51
SUPPLY OPEN
72
Supply sensor open
Check the supply sensor and connection.