71

LP-294 REV. 2.20.14

A13

State error

19

Internal software error

Exchange BCU.

A14

Rom error

20

Internal software error

A14

Rom error C

21

Internal software error

A15

Air sw not open

22

Air pressure switch not working

Check air switch, hose to air switch
(water), and wiring to BCU. Check
Menu settings.

A16

15MS XRL error

23

3 timing errors

Reset.

A17

Air sw not closed

24

Air pressure switch not working

Check air switch, hose to air switch
(water), and wiring to BCU. Check
Menu settings.

A18

Max Temp. Error

25

External overheat protection is
activated

Check overheat sensor, wiring, supply
settings, and supply controller settings.

A19

Stack error

26

Internal software error

Exchange BCU.

A20

Flame out too late

27

Flame still present 10 sec. after
closing the gas valve

Check position of ionization pin, clean
surface of ionization pin, Check the gas
valve tightness.

A21

False Flame

28

Flame is detected before ignition

Check the gas connection and gas
valve. Check position of ionization pin.
Reset. If error is not corrected,
exchange BCU.

A22

20MS XRL error

29

Internal software error

Reset the boiler.

A23

41MS XRL error

30

Internal software error

A24

Too many flame failures

31

Ten times flame loss during one
demand

Check the gas connection. Check
ionization wiring, pin, and position.
Check gas pressure.

A25

Flow switch not closed

32

Flow switch not working / No flow

Check the flow switch.

A26

Flow switch not open

33

Flow switch not working / No flow

A27

Flag byte integrity

34

Internal software error

Exchange BCU.

A28

AD Hi cpl.

35

Internal software error

A29

AD Lo cpl.

36

Internal software error

A30

Register error

37

Internal software error

A30

CPSM Error

37

Internal software error

Table 42

– Lockout Error Codes

2. BLOCKING ERROR CODES

DISPLAY

CODE

ERROR

INT.

CODE

DESCRIPTION

POSSIBLE SOLUTION

E31

REFHI TOO LO

50

Internal hardware error

Check Field Connection Board on
shortcuts, otherwise exchange BCU.

E32

REFHI TOO HI

51

E33

REFLO TOO LO

52

E34

REFLO TOO HI

53

E35

FALSE FLAME

54

Flame is detected in a state in which
no flame is allowed to be seen

Check the gas connection and gas valve.
Check position of ionization pin. Reset. If
error is not corrected, exchange BCU.

E36

WATER LEVEL DETECT

55

Low water level detected

Check the water pressure and sensor.
(N/A)

E36

WATER LEVEL MEAS

56

Low water level measurement error

E36

LOW WATER CUTOFF

57

Low water sensor error

E37

LOW WATER PRESSURE

58

Low water pressure error

E38


WATER PRESSURE
SENSOR

59


Low water pressure depending on
BCU settings


Check the water pressure and sensor.
(N/A). Check menu setting.

E39

FLUE GAS ERROR

60

Flue gas temperature error

Check the flue switch or sensor. Check
wiring. Check heat exchanger.

E41

BLOCKED DRAIN

62

Blocked drain switch is active

Check and clean condensate trap and
condensate piping.

E43

WD FREQ ERROR

64

Not a correct frequency signal or no
communication with the WD

Check the supply voltage and frequency.
Exchange BCU.

E44

PHASE ERROR

65

Hot neutral reversed

Line not connected correctly.

E45

NET FREQ ERROR

66

Net frequency error detected.

Check the supply voltage and frequency.
Exchange BCU.

E46

FAULTY EARTH ERROR

67

Faulty earth connection

Check the earth connections of the boiler
and BCU.

E47

WD COMM ERROR

68

Watchdog communication error

Exchange the BCU.

E51

SUPPLY OPEN

72

Supply sensor open

Check the supply sensor and connection.