A. BOILER STATUS INSTALLER

After selecting “Boiler Status Inst.” at the Installer Menu screen, the following options are available.

SCREEN

DESCRIPTION

BOILER STATUS INST.
Fan
Actual 16.22g/s
Low power 2.2g/s

This screen shows the current actual mass flow and actual recorded mass flow at low power.

Pressing the

▼ key allows the Installer to view more data.

BOILER STATUS INST. 
Fan
Ignition 23.60g/s
HiPower 16.22g/s

This screen shows the actual mass flow needed for ignition and the actual recorded mass flow at
high power.

Pressing the

▼ or ▲ keys allows the Installer to view more data or return to the previous screen.

BOILER STATUS INST. 
Flame
Ionization 9.0uA
Loss xxxxx 

This screen displays the actual ionization current and number of flame losses after flame
recognition.

Pressing the

▼ or ▲ keys allows the Installer to view more data or return to the previous screen.

BOILER STATUS INST. 
Ignition Attempts
With flame xxxxx
No flame xxxxx 

This screen details the number of times the flame appeared during an ignition cycle, and where the
boiler restarted due to weak gas quality of low gas pressure.

Pressing the

▼ or ▲ keys allows the Installer to view more data or return to the previous screen.

BOILER STATUS INST. 
Run time
CH xxxxxxxhr
DHW xxxxxxxhr

This screen shows the total boiler run time for central heating and domestic hot water in hours.

Pressing the

▼ or ▲ keys allows the Installer to view more data or return to the previous screen.

BOILER STATUS INST. 
Run time
pwrON xxxxxxxdays
Service xxxxdays

This screen shows the run time in days for total power on and the amount of time until next service,
as set by the service reminder.

NOTE:
Take care not to set the service reminder for a holiday.

Pressing the

▼ or ▲ keys allows the Installer to view more data or return to the previous screen.

BOILER STATUS 
Fan Speed 5600 rpm
GV act. 650 hstep
FlameIon. 9.0 uA

This screen shows actual fan speed, actual gas valve position, and actual ionization current in uA.

Pressing the

▼ or ▲ keys allows the Installer to view more data or return to the previous screen.

ERRORhist No.## E##
error description
Block. zz hrs ago

This screen displays the last 16 errors. No. ## is the number error on the list. E## indicates a
blocking error code. An error description is shown, as well as the time that has passed between
now and the error code. Pressing the 

key displays the interval between errors (“yyhrs after

No.zz”). The first error appears twice in the list (min, hrs, day, wk). Scrolling through all last 16
errors is possible by pressing the  key.

Pressing the

▼ or ▲ keys allows the Installer to view more data or return to the previous screen. Pressing the  key leaves Error

history and returns to the Installer Menu.

ERRORhist No.## A##
error description
Lock. zz hrs ago

This screen displays the last 16 errors. No. ## is the number error on the list. A## indicates a
lockout error code. An error description is shown, as well as the time that has passed between now
and the error code. Pressing the 

key displays the interval between errors (“yyhrs after No.zz”).

The first error appears twice in the list (min, hrs, day, wk). Scrolling through all last 16 errors is
possible by pressing the  key.

Pressing the

▲ key allows the Installer to return to the previous screen. Pressing the  key leaves Error history and returns to the

Installer Menu.