CASCADE SETTINGS 
Start Differential
to System Setpoint
9

o

F

Allows the installer to set the system setpoint differential. Default is 9

o

F. Range: 1

– 15

o

F.

Pressing the

▼ or ▲ keys allows the Installer to view and/or adjust more data or return to the previous screen.

CASCADE SETTINGS 
Stop Differential
to System Setpoint
5

o

F

Prevents the system from overshooting temperatures by stopping all boilers once the stop
differential is met. Default is 5

o

F. Range: 1

– 15

o

F.

Pressing the

▼ or ▲ keys allows the Installer to view and/or adjust more data or return to the previous screen.

CASCADE SETTINGS 
Next Boiler
Start Delay time
_3min

If the system setpoint temperature (minus start differential) is not reached, or the first boiler has too
high a modulation range, the next boiler is started after a certain delay time.
Default is 3 minutes. Range: 1

– 15 minutes.

Pressing the

▼ or ▲ keys allows the Installer to view and/or adjust more data or return to the previous screen.

CASCADE SETTINGS 
Last Boiler
Stop Delay time
_3min

If the boilers operate at the minimum switching rate and the system setpoint temperature is too
high, this option determines when the last boiler will stop. Default is 3 minutes. Range: 1

– 15

minutes.

Pressing the

▼ or ▲ keys allows the Installer to view and/or adjust more data or return to the previous screen.

CASCADE SETTINGS 
Max increased
Boiler Offset
10

o

F

Maximum boiler offset temperature above the system setpoint used by the intelligent PID
cascading controller to meet system setpoint. Default is 10

o

F. Range: 0

– 36

o

F.

Pressing the

▼ or ▲ keys allows the Installer to view and/or adjust more data or return to the previous screen.

CASCADE SETTINGS 
Min decreased
Boiler Offset
20

o

F

Minimum boiler offset temperature below the system setpoint used by the intelligent PID cascading
controller to meet system setpoint.
Default is 20

o

F. Range: 0

– 36

o

F.

Pressing the

▼ or ▲ keys allows the Installer to view and/or adjust more data or return to the previous screen.

CASCADE SETTINGS 
Delay Factor for
Boiler Offset
2

Time factor is mul

tiplied with “next boiler start delay time” and determines when the intelligent PID

cascading controller becomes active. Default is 2. 0 = Disabled.

Pressing the

▼ or ▲ keys allows the Installer to view and/or adjust more data or return to the previous screen.

CASCADE SETTINGS 
Next Boiler
Start Rate
80

When this modulation range is reached by one or more boilers, the next boiler is started after the
“next boiler start delay time”.
Default is 80. Range: 10

– 100.

Pressing the

▼ or ▲ keys allows the Installer to view and/or adjust more data or return to the previous screen.

CASCADE SETTINGS 
Last Boiler
Stop Rate
40

When this modulation range is reached by one or more boilers, the last boiler is stopped after the
“last boiler stop delay time”. Default is 30. Range: 10 – 100.

Pressing the

▼ or ▲ keys allows the Installer to view and/or adjust more data or return to the previous screen.

CASCADE SETTINGS 
Boiler
Rotation Interval
1 day

The first boiler is changed after the rotation interval “1 – 5 days”. If set to “0” no rotation occurs. If
one boiler is dedicated to DHW, it will always be the last boiler in the rotation interval. Default is 1
day. Range: 0

– 30 days.

Pressing the

▼ or ▲ keys allows the Installer to view and/or adjust more data or return to the previous screen.

CASCADE SETTINGS 
Boilers for DHW

Boiler Address All

This option is used to select boilers dedicated to DHW. Options:
ALL = CH and DHW are connected in parallel
2

– 16 = Certain boilers are dedicated to DHW

Default is ALL. Range: All, 1

– 16.

Pressing the

▼ or ▲ keys allows the Installer to view and/or adjust more data or return to the previous screen.

CASCADE SETTINGS 
System Pump
Post Pump Time
30sec

Selects the time the system pump will run after burner stop. Default is 30 seconds.
Range: 1

– 90 seconds.

Pressing the

▲ key allows the Installer to return to the previous screen.

Table 29

– Installer Menu – Cascade Settings Screens