Page 69: Troubleshooting, Part 14 – troubleshooting
69
LP-294 REV. 2.20.14
DHW SETTINGS
CH/DHW Priority
>Switch DHW-Prio
Time 30min
CH/DHW Priority sets the heating priority of the boiler.
The following options can be selected:
Time - Priority changes after time.
CH-Prio - Central heating always takes priority.
DHW-Prio - Domestic hot water always takes priority.
Defaults is DHW-Prio, and 30 minutes. Range: 1
– 60 Minutes.
Table 39
– DHW Settings Quick Start-Up
Once the CH/DHW Priority is set, press ENTER to save. Press the key to exit the Installer Menu return to the User Menu.
E. USER MENU BOILER SETTINGS
To view Boiler Settings: At the Main Screen, you can enter the User Menu by pressing the key. At the initial User Menu screen, press
the ENTER key when the
> icon is in line with Boiler Settings, and a series of Boiler Settings options can be accessed. These options
and corresponding screens are described below.
SCREEN
DESCRIPTION
BOILER SETTINGS
Central Heating
Setpoint
Outdoor Reset 180
o
F
In a cascaded
system, “CH-Cascade” is shown. OutdoorReset is only shown when CH-mode 1 or
2 is used. This indicates that the setpoint cannot be changed. When not used, the installer can set
the setpoint for central heating.
Pressing the
▼ key allows the User to view more data.
BOILER SETTINGS
DHW-Store
Setpoint
119
o
F
Visible in DHW mode 1 and 2.
Displays the storage tank temperature setpoint if an indirect sensor is used.
The factory installed default setpoint is 119
o
F. Range: 104
– 160
o
F.
Table 40
– User Menu - Boiler Settings – Quick Start-Up
F. CASCADE FOLLOWER MAIN SCREENS
To view Cascade Follower Main Screens: Press the key to return to the Main Menu
SCREEN
DESCRIPTION
BOILER ##
STANDBY: NO DEMAND
160°F
This display is visible at single and cascaded boilers.
“BOILER ##” will only appear in cascaded
systems. ## stands for boiler address. Press
the ▼ key at the cascade master to view the outputs
of cascade followers. In this screen the boiler is in standby. There are no active outputs.
FPBSG BOILER ##
CENTRAL HEATING
100% 160°F
This screen displays operation status (modulation range and actual supply temperature) and active
outputs of the control. “BOILER ##” will only appear in cascaded systems. ## stands for boiler
address. Press
the ▼ key at the cascade master to view the outputs of cascade followers. Active
outputs of control are:
F
– Flame P - Pump for CH or general pump
B
– Blower S - Spark
G - Gas valve D - DHW Pump or 3 WV
L
– Limited Modulation
Table 41
– Boiler Main Screens – Quick Start-Up
PART 14 – TROUBLESHOOTING
When servicing or replacing any components of this boiler, be certain that:
The gas is off.
All electrical power is disconnected.
When servicing or replacing components that are in direct contact with boiler water, be certain that:
There is no pressure in the boiler. (Pull the release on the relief valve. Do not depend on the pressure gauge reading.
The boiler water is not hot.
The electrical power is disconnected.