DHW SETTINGS 
CH/DHW Priority

>Switch DHW-Prio

Time 30min

CH/DHW Priority sets the heating priority of the boiler.
The following options can be selected:
Time - Priority changes after time.
CH-Prio - Central heating always takes priority.
DHW-Prio - Domestic hot water always takes priority.
Defaults is DHW-Prio, and 30 minutes. Range: 1

– 60 Minutes.

Table 39

– DHW Settings Quick Start-Up

Once the CH/DHW Priority is set, press ENTER to save. Press the  key to exit the Installer Menu return to the User Menu.

E. USER MENU BOILER SETTINGS

To view Boiler Settings: At the Main Screen, you can enter the User Menu by pressing the  key. At the initial User Menu screen, press
the ENTER key when the

> icon is in line with Boiler Settings, and a series of Boiler Settings options can be accessed. These options

and corresponding screens are described below.

SCREEN

DESCRIPTION

BOILER SETTINGS
Central Heating
Setpoint
Outdoor Reset 180

o

F 

In a cascaded

system, “CH-Cascade” is shown. OutdoorReset is only shown when CH-mode 1 or

2 is used. This indicates that the setpoint cannot be changed. When not used, the installer can set
the setpoint for central heating.

Pressing the

▼ key allows the User to view more data.

BOILER SETTINGS 
DHW-Store
Setpoint
119

o

F

Visible in DHW mode 1 and 2.
Displays the storage tank temperature setpoint if an indirect sensor is used.
The factory installed default setpoint is 119

o

F. Range: 104

– 160

o

F.

Table 40

– User Menu - Boiler Settings – Quick Start-Up

F. CASCADE FOLLOWER MAIN SCREENS

To view Cascade Follower Main Screens: Press the  key to return to the Main Menu

SCREEN

DESCRIPTION

BOILER ## 

STANDBY: NO DEMAND
160°F

This display is visible at single and cascaded boilers.

“BOILER ##” will only appear in cascaded

systems. ## stands for boiler address. Press

the ▼ key at the cascade master to view the outputs

of cascade followers. In this screen the boiler is in standby. There are no active outputs.

FPBSG BOILER ## 

CENTRAL HEATING
100% 160°F

This screen displays operation status (modulation range and actual supply temperature) and active
outputs of the control. “BOILER ##” will only appear in cascaded systems. ## stands for boiler
address. Press

the ▼ key at the cascade master to view the outputs of cascade followers. Active

outputs of control are:
F

– Flame P - Pump for CH or general pump

B

– Blower S - Spark

G - Gas valve D - DHW Pump or 3 WV
L

– Limited Modulation

Table 41

– Boiler Main Screens – Quick Start-Up

PART 14 – TROUBLESHOOTING

When servicing or replacing any components of this boiler, be certain that:

The gas is off.

All electrical power is disconnected.

When servicing or replacing components that are in direct contact with boiler water, be certain that:

There is no pressure in the boiler. (Pull the release on the relief valve. Do not depend on the pressure gauge reading.

The boiler water is not hot.

The electrical power is disconnected.