APPENDIX B
Wire Gauge Factoring
Remote Power Supply
The iMXDa/iEXDa requires adequate voltage and current for proper operation.
Resistance is created by the length and gauge (size) of the wire being used.
An accurate estimated distance from the power supply to the opening is crucial.
For optimum operation the correct size gauge wire must be used.
The devices used operate the best with the least amount of resistance on the source.
Using the correct gauge wires protects against large voltage and current (load) losses.
The gauge is determined by the wire distance, voltage and current of all devices.
Determining Wire Gauge
Follow Example A (12VDC system) and Example B (24VDC system) below.
Use Table B-1 and Table B-2 to determine the correct wire gauge for the application.
Example A: (an iMXDa used in a 12VDC system)
Devices Used
Amps (12VDC)
Progressive Totals
iMXDa
0.370
0.370
DK-26 Access
0.160
0.530
MK Bypass/Reset
0.020
0.550
Total Current Rounded Up (Table 1)
0.600A
Using Table B-1 (12VDC) Find: - Current Draw .600 Amps
- Wire Distance 200 Feet (One-Way)
Solution: 18 Gauge is indicated for proper installation
Example B: (an iEXDa used in a 24VDC system)
Devices Used
24VDC Amps
Progressive Totals
iEXDa
0.270
0.270
TSB Touch Bar
0.025
0.295
DK-11 Access
0.070
0.365
Total Current Rounded Up (Table 2)
0.400A