beautypg.com

0 meter technical specifications, 4 pulse type and value – E-Mon E50-6003200R*KIT User Manual

Page 9

background image

CLASS 5000 METER

9

62-0392-03

2.4 Pulse Type and Value

The pulse outputs provided by the Class 5000 meter are watt-hours and var-hours.

Output 1 is the watt-hour pulse and Output 2 is the var-hour pulse. The pulse value is

dependant on the amperage size of the meter. See the chart below for the values also

true for expansion board pulse output.

3.0 METER TECHNICAL SPECIFICATIONS

Ordering Information: Define brand, class, input voltage, current sensor rating,

enclosure, protocols/options, expanded feature package, and sensor type in the format

A-BB-CCC-DDDD-E-FF-G-HHH, where:

A = Brand: E for E-Mon

BB = designates Class: 3200 (32), 3400 (34), or 5000 (50) meter

CCC = input voltage: (208, 480, 600, 120 volt for high voltage applications only)

DDDD = current sensor rating: (100, 200, 400, 800, 1600, 3200, 25HV)

E = enclosure: J = metal (type 1), R = non-metallic (type 4X)

FF= protocol option:

G = Expanded Feature Package: package = X, no package = “blank”

(on Class 3400 only)

HHH= Sensor Type: kit=split-core, scs= solid-core, non-supplied blank”

“-SP ”= 1 or 2 Phase

Meter Amps

Watt-hours / pulse

Var-hours / pulse

100

1.95313

1.95313

200

3.90625

3.90625

400

7.8125

7.8125

800

15.625

15.625

1800

31.25

31.25

3200

62.5

62.5

M33273

EXAMPLE:

E 50 208

400

R

05 KIT

CLASS 5000 METER

INPUT VOLTAGE (208V)

CURRENT RATING (400A)

ENCLOSURE (4X)

EZ7/BACnet IP/NO MODEM

E-MON

SPLIT CORE SENSORS