CLASS 5000 METER

57

62-0392-03

1.

To clear single meter kWh/kVARh, select reset kW/kWh on the display menu of the
meter. This function will also reset external inputs. Jumper J6 must be closed.
Remove J6 after changes have been completed.

2.

External inputs are standard on Class 5000 meters and optional on Class 3400
meters (Part of Expanded Feature Package). To clear external inputs, select reset
kW/kWh on the display menu of the meter. This function will also reset kW/kVARh.
Jumper J6 must be closed. Remove J6 after changes have been completed.

nvoPhase_AngleA

SNVT_angle_f

Phase angle,

phase A

Degree

R

nvoPhase_AngleB

SNVT_angle_f

Phase angle,

phase B

Degree

R

nvoPhase_AngleC

SNVT_angle_f

Phase angle,

phase C

Degree

R

nvoReserve_A

SNVT_count_f

Reserve A

No units

R

nvoReserve_B

SNVT_count_f

Reserve B

No units

R

nvoReserve_C

SNVT_count_f

Reserve C

No units

R

nvoExt_Input_1

2

SNVT_count_f

External

Input 1

Pulse

R

nvoExt_Input_2

2

SNVT_count_f

External

Input 2

Pulse

R

Lonworks SNVT Types Point Map: CL5000