c. External Switch Mechanism/In-Line Fuse Installation.

To ensure a safe installation, the Class 5000 meter requires an external

switch mechanism, such as a circuit breaker, be installed on the Class 5000

MAINS input wiring. The switch mechanism must be installed in close prox-

imity to the meter and easily reachable for the operator. This device must

also be marked as the disconnecting device for the Class 5000 meter. Install

1/10 Amp Slow Activation in-line fuses with the suitable voltage rating for

each conductor phase at the MAINS input to the meter. The fuses must be

labeled to indicate voltage and current rating as well as element characteris-

tics. The fuse element must be slow activating type.

d. Connect the three AC main power wires (Phases A, B and C) to their respec-

tive positions as labeled on terminal block TB1 and tighten to 7 in-lb. After all

conductors are connected to each of their respective terminal block positions

and tightened down, verify that each terminal block screw is securely fas-

tened by gently tugging on each conductor.

NOTE: On Single phase connections: Connect two AC main power wires to

phases A and B - Connect jumper from B to C - factory installed for “-SP”

option. Verify that no conductor wires are frayed or shorting to adjacent ter-

minal block positions.

e. Turn ON the AC main power input. The meter display will light up and scroll

through 7 displays. Each display is visible for 5 seconds. Display screens are

as follows:

Screen 1 - Total kilowatt-hours (kWh) consumed

Screen 2 - Peak demand (kW) with date & time stamp

Screen 3 - Actual load (kW) with preset date & time

Screen 4 - Average current (amps) per phase

Screen 5 - Average voltage (volts) per phase

Screen 6 - Average voltage (volts) phase to phase

Screen 7 - Power factor (PF) per phase

f. Verify the voltage readings on Screen 5 using an AC voltmeter. Typical read-

ings shown below are measured phase to neutral for 4 wire and phase to

phase for 3 wire. Readings should be +/- 10% of nominal.

NOTE: Meters are powered by phases A and B. The displayed voltages will be the

measured AC voltage between phases.

Meter Type

Nominal Voltage

Limits (+/- 10%)

120/208V, 3ø, 4 Wire
120/240V, 1ø, 3 Wire

120V, 1ø, 2 Wire

120 VAC (L-N)

108 to 132 VAC

277/480V, 3ø, 4 Wire

277V, 1ø, 2 Wire

277 VAC (L-N)

249 to 305 VAC

240V, 3ø, 3 Wire

240 VAC (L-L)

216 to 264 VAC

400V, 3ø, 4 Wire

230 VAC (L-N)

207 to 253 VAC

480V, 3ø, 3 Wire

480 VAC (L-L)

432 to 528 VAC

600V, 3ø, 4 Wire

347 VAC (L-N)

312 to 380 VAC