E-Mon E50-6003200R*KIT User Manual
Page 15
CLASS 5000 METER
15
62-0392-03
c. External Switch Mechanism/In-Line Fuse Installation.
To ensure a safe installation, the Class 5000 meter requires an external
switch mechanism, such as a circuit breaker, be installed on the Class 5000
MAINS input wiring. The switch mechanism must be installed in close prox-
imity to the meter and easily reachable for the operator. This device must
also be marked as the disconnecting device for the Class 5000 meter. Install
1/10 Amp Slow Activation in-line fuses with the suitable voltage rating for
each conductor phase at the MAINS input to the meter. The fuses must be
labeled to indicate voltage and current rating as well as element characteris-
tics. The fuse element must be slow activating type.
d. Connect the three AC main power wires (Phases A, B and C) to their respec-
tive positions as labeled on terminal block TB1 and tighten to 7 in-lb. After all
conductors are connected to each of their respective terminal block positions
and tightened down, verify that each terminal block screw is securely fas-
tened by gently tugging on each conductor.
NOTE: On Single phase connections: Connect two AC main power wires to
phases A and B - Connect jumper from B to C - factory installed for “-SP”
option. Verify that no conductor wires are frayed or shorting to adjacent ter-
minal block positions.
e. Turn ON the AC main power input. The meter display will light up and scroll
through 7 displays. Each display is visible for 5 seconds. Display screens are
as follows:
Screen 1 - Total kilowatt-hours (kWh) consumed
Screen 2 - Peak demand (kW) with date & time stamp
Screen 3 - Actual load (kW) with preset date & time
Screen 4 - Average current (amps) per phase
Screen 5 - Average voltage (volts) per phase
Screen 6 - Average voltage (volts) phase to phase
Screen 7 - Power factor (PF) per phase
f. Verify the voltage readings on Screen 5 using an AC voltmeter. Typical read-
ings shown below are measured phase to neutral for 4 wire and phase to
phase for 3 wire. Readings should be +/- 10% of nominal.
NOTE: Meters are powered by phases A and B. The displayed voltages will be the
measured AC voltage between phases.
Meter Type
Nominal Voltage
Limits (+/- 10%)
120/208V, 3ø, 4 Wire
120/240V, 1ø, 3 Wire
120V, 1ø, 2 Wire
120 VAC (L-N)
108 to 132 VAC
277/480V, 3ø, 4 Wire
277V, 1ø, 2 Wire
277 VAC (L-N)
249 to 305 VAC
240V, 3ø, 3 Wire
240 VAC (L-L)
216 to 264 VAC
400V, 3ø, 4 Wire
230 VAC (L-N)
207 to 253 VAC
480V, 3ø, 3 Wire
480 VAC (L-L)
432 to 528 VAC
600V, 3ø, 4 Wire
347 VAC (L-N)
312 to 380 VAC
- E50-6001600R*KIT E50-600800-R*KIT E50-600400-R*KIT E50-600200-R*KIT E50-600100-R*KIT E50-4803200R*KIT E50-4801600R*KIT E50-480800-R*KIT E50-480400-R*KIT E50-480200-R*KIT E50-480100-R*KIT E50-4003200R*KIT E50-4001600R*KIT E50-400800-R*KIT E50-400400-R*KIT E50-400200-R*KIT E50-400100-R*KIT E50-2083200R*KIT E50-2081600R*KIT E50-208800-R*KIT E50-208400-R*KIT E50-208200-R*KIT E50-208100-R*KIT