6.8 RS-232 Communications
6.8.1 Hardwired System using the RS-232 Communication Key
The RS-232 communications key allows you to connect Class 5000 meters to a
personal computer that has the E-Mon Energy™ software installed. The computer
communicates with the meters through the RS-232 key.
The RS-232 key must be located within 15 feet of the host computer.
Fig. 13. RS-232 Configuration.
6.8.2 Connecting the RS-232 Key to the Computer
The RS-232 key is supplied with:
a. (1) 8-conductor cable fitted with RJ-45 plugs
b. (1) DB-9 serial COM port adapter
c. (1) AC adapter that converts 120VAC to 9VDC for powering the RS-232 key
Connection Steps:
1. Connect the 8-conductor cable to the left-side jack (labeled “RS232”) on the rear
panel of the RS-232 key.
2. Connect the appropriate COM port adapter (DB-9) to the serial port on the back
of the computer. Plug the 8-conductor cable from the RS-232 key into the COM
port adapter.
3. Connect the provided AC adapter into the rear panel input on the RS- 232 key.
Plug the adapter into a 120VAC outlet. On the front panel of the RS-232 key, two
LEDs (POWER ON and AC ON) will light up.
CHANNEL 2
~~
~~
CHANNEL 3 UP TO 4000
FEET TOTAL
RS-232
KEY*
RS-232 SERIAL
PORT COM1
OR COM2
UP TO 52
CLASS 5000
METERS
M33275
UP TO 4000
FEET TOTAL
UP TO 52
CLASS 5000
METERS
CHANNEL 1
AC ADAPTER
PC
15 FEET MAX
- E50-6001600R*KIT E50-600800-R*KIT E50-600400-R*KIT E50-600200-R*KIT E50-600100-R*KIT E50-4803200R*KIT E50-4801600R*KIT E50-480800-R*KIT E50-480400-R*KIT E50-480200-R*KIT E50-480100-R*KIT E50-4003200R*KIT E50-4001600R*KIT E50-400800-R*KIT E50-400400-R*KIT E50-400200-R*KIT E50-400100-R*KIT E50-2083200R*KIT E50-2081600R*KIT E50-208800-R*KIT E50-208400-R*KIT E50-208200-R*KIT E50-208100-R*KIT