beautypg.com

Caution, Warning, 0 introduction – E-Mon E50-6003200R*KIT User Manual

Page 4

background image

CLASS 5000 METER

62-0392-03

4

1.0 INTRODUCTION

The E-Mon D-Mon® Class 5000 meter is a 3-phase meter with communications. The

device is used to monitor electric power usage of individual loads after the utility meter

and store kW and kVAR data for automatic meter reading. The Class 5000 meter is

dual protocol capable and provides both RS485 and Ethernet communications.

Installation must only be performed by qualified personnel and in accordance with

these instructions and all applicable local and national electrical codes. E-Mon and its

representatives assume no responsibility for damages or injury resulting from the

improper installation of this meter.

Verify the input voltage rating and configuration on the unit panel label to ensure that it

is suitable for the intended electrical service. Class 5000 meters labeled for 120/208V

service MUST NOT be installed on service feeds of 277/480 volts or 347/600 and vice

versa. Verify that the Class 5000 meter’s current sensors are sized suitably for the load

to be monitored. Compare the color of the arrows on the current sensors to the chart

below to confirm the correct current sensor is being used.

CAUTION

Internal circuit card components are extremely sensitive to electrostatic

discharge. Prior to handling or touching internal circuitry, discharge any static

buildup on your person. To discharge yourself, touch a grounded metal object

such as conduit or an earth grounded metal enclosure.

WARNING

Use of this instrument, Class 5000, in a manner inconsistent with this manual

or not specified by the manufacturer in writing, can cause permanent damage

to the unit and/or serious injury to the operator. The protection and safety

features provided by this equipment may become impaired or otherwise

compromised.

NOTE: If any trouble arises during installation or functional verification operations, do

not immediately remove unit. Before removing the unit, contact E-Mon’s tech-

nical support department at (800) 334-3666. E-Mon’s technical department

will assist you in detailed troubleshooting of the Class 5000 installation.

Sensor Arrow Color Code

Sensor Rating

Brown

100 A

Red

200 A

Yellow

400 A

Black

800 A

Blue

1600 A

White/Black 3200

A