beautypg.com

1 main power board – E-Mon E50-6003200R*KIT User Manual

Page 6

background image

CLASS 5000 METER

62-0392-03

6

2.1 Main Power Board

Connections to this board include the MAIN Power Input and current sensors. The

MAIN Power Input terminals are positions one through four on the four position screw

terminal block, TB1. These terminals are covered with a protective shield for safety

purposes. The current sensor assemblies interface to the TB2, TB3 and TB4. Each

terminal block corresponds to an input voltage phase; care must be exercised to

ensure that each current sensor is connected to the correct terminal block. One three

terminal screw connector(TB42) is provided for RS-485 communications. One RJ-45

jack (J8) is provided for 10/100-base T Ethernet.

The contact is a solid-state switch for the phase-loss alarm function. Switching is

limited to 100 ma (0.1 amp) and voltage should not exceed 60 Volts AC or DC.

The (N.O.) contact closes within the meter due to the loss any one of the three lines of

voltage inputs to the meter. The contact closure may be used to activate an audible

alarm, light, control coil, or other indicator device. This alerts appropriate personnel to

the loss of voltage. An emergency phone dialer may also be programmed to send

notification automatically by phone, text, or pager. Alarming devices to be supplied by

others and are not included by with the E-Mon Class 5000 meter.

One two terminal screw connector provides phase loss alarming.

There are also two headers present for adding option cards. Header J3 is 20 positions

for use with an I/O board with up to two relays, two pulse inputs and two pulse out puts.

Header J4 is a 10 positions for use with modem and LonWorks TP/FT-10.

Fig. 2. Main Power Board.

M33271

TB1

POSITIONS

POSITIONS

6-10

PHASE LOSS

TB42

J3

J4

J8