Page 29

background image

CLASS 5000 METER

29

62-0392-03

6.9.3 Baud Rate Selection

The communication baud rate is selected by means of a jumper on the circuit board.

There are four (4) selections: 9600 (factory default), 19200, 38400, and 76800.

1. Select 9600 when using the Class 5000 meter with a modem.

2. The baud rate on the meter must always match the baud rate selected in the E-

Mon Energy software; otherwise, communications will not work.

3. After a baud rate change, press CPU Reset to register the change.

4. All meters in the daisy-chain circuit must be set at the same baud rate.

5. The DIP switch is located above the RS-485 terminals.

6. Using other than 9600 BAUD will reduce the maximum cable length allowed for

communication.

NOTE: USE ONLY POSITIONS 3 AND 4 - DO NOT CHANGE ANY OTHER

POINTS.

The selections are noted below.

Fig. 15. Baud Rate Selection

3

4

Baud rate

ON ON

9600 (EZ-7, modbus RTU, BACnet MS/TP)

OFF ON

19200 (EZ-7, modbus RTU, BACnet MS/TP)

ON OFF 38400 (Modbus RTU, BACnet MS/TP)
OFF

OFF 78600 (Bacnet MS-TP)