Daily inspection, 7daily inspection – MaxPower Corp Toshiba G9000 Series User Manual
Page 70
60
G9000 Installation and Operation Manual
7
DAILY INSPECTION
Please perform the daily inspection while the UPS is running. The daily inspection items are
shown in Table 7.1.
The customers can only inspect exterior or environment of cabinet. When the
customers want to perform the detailed inspection, contact the Authorized Toshiba
Service Representatives or call Toshiba International Corporation at
1-800-231-1412.
TABLE 7.1 How to perform daily inspection
No
.
Subject
Procedure
Criteria and/or Action needed
Term
Period
Method/Tool
1.
Environmental
ambient
Dust or Gas
Daily
Visual check and
smelling
Ventilate room atmosphere if dusty or
smelling gas.
Dewdrops
Condensation
Daily
Visual check
Fix the dripping source
Dehumidify upon necessity.
Temperature
Humidity
Daily
Thermometer
hygrometer
Temperature: 32
– 104 F Humidity: 30 –
90%
No condensation.
To be controlled at 77 F or about by
A/C.
2.
Cabinet
Construction
Vibration or
Audible noise
Daily
Touch and
hearing
Check if fans have irregular sound.
Contact service representative in case
of abnormalities.
Overheating
When
needed
Touching exterior
Contact service representative in case
of abnormalities.
Air filter clog
When
needed
Visual check
Clean/wipe if clogged or dusty.
3.
Operation
LCD sharpness
Brightness
Left-bottom LED
Daily
Visual check
No characters faded, illegible or any
other abnormalities.
Left-bottom LED should be green.
Contact service representative when
the LED shows red with the backlight
lost.
Indication terms:
Output voltage
Output current
AC
input
voltage
Output frequency
Battery voltage
Battery current
DC voltage
Daily
Visual check
Check indication terms/values if within
the adequate window.
Also check indication meters on
surface of optional cabinet, if installed.
4.
LEDs
4 status LEDs
Daily
Visual check
Check if LEDs turn on, off or flash
according to the operation.
2 fault LEDs
Daily
Visual check
If UPS fault LED turns on, scroll the
screen to see fault codes and record
the codes.
Contact service representative to tell
about fault codes and UPS symptom.
!
NOTE