beautypg.com

Daily inspection, 7daily inspection – MaxPower Corp Toshiba G9000 Series User Manual

Page 70

background image

60

G9000 Installation and Operation Manual

7

DAILY INSPECTION

Please perform the daily inspection while the UPS is running. The daily inspection items are

shown in Table 7.1.

The customers can only inspect exterior or environment of cabinet. When the

customers want to perform the detailed inspection, contact the Authorized Toshiba

Service Representatives or call Toshiba International Corporation at

1-800-231-1412.



TABLE 7.1 How to perform daily inspection

No

.

Subject

Procedure

Criteria and/or Action needed

Term

Period

Method/Tool

1.

Environmental

ambient

Dust or Gas

Daily

Visual check and

smelling

Ventilate room atmosphere if dusty or

smelling gas.

Dewdrops

Condensation

Daily

Visual check

Fix the dripping source

Dehumidify upon necessity.

Temperature

Humidity

Daily

Thermometer

hygrometer

Temperature: 32

– 104 F Humidity: 30 –

90%

No condensation.

To be controlled at 77 F or about by

A/C.

2.

Cabinet

Construction

Vibration or

Audible noise

Daily

Touch and

hearing

Check if fans have irregular sound.

Contact service representative in case

of abnormalities.

Overheating

When

needed

Touching exterior

Contact service representative in case

of abnormalities.

Air filter clog

When

needed

Visual check

Clean/wipe if clogged or dusty.

3.

Operation

LCD sharpness

Brightness

Left-bottom LED

Daily

Visual check

No characters faded, illegible or any

other abnormalities.

Left-bottom LED should be green.

Contact service representative when

the LED shows red with the backlight

lost.

Indication terms:

Output voltage

Output current

AC

input

voltage

Output frequency

Battery voltage

Battery current

DC voltage

Daily

Visual check

Check indication terms/values if within

the adequate window.

Also check indication meters on

surface of optional cabinet, if installed.

4.

LEDs

4 status LEDs

Daily

Visual check

Check if LEDs turn on, off or flash

according to the operation.

2 fault LEDs

Daily

Visual check

If UPS fault LED turns on, scroll the

screen to see fault codes and record

the codes.

Contact service representative to tell

about fault codes and UPS symptom.

!

NOTE