Warning 4 – MaxPower Corp Toshiba G9000 Series User Manual

Page 15

background image

G9000 Installation and Operation Manual

5

This UPS does not include a Bypass input circuit breaker (MCCB) to protect

the bypass circuit. The Bypass input circuit breaker (MCCB) is to be field

supplied and installed. Recommended Breaker (MCCB)'s Specifications are

as follows:

TABLE 1.2

Rating of Bypass Input Circuit Breaker

Capacity (kVA) Bypass Voltage (Vac) Bypass Rating (Aac)

Breaker (A)

80

480

96

125

100

480

120

150

160

480

192

250

225

480

271

350

AC input and AC output overcurrent protection and disconnect devices shall be field

supplied and installed. The DC circuit breaker (MCCB) shall be field supplied and

installed. The overcurrent protection device should be installed in the Battery cabinet

and rated as indicated in TABLE 1.6.

Note: The DC input overcurrent protection (Battery disconnect breaker) hereinafter will

be referred

as “CB2”.

WARNING 4

!

NOTE