MaxPower Corp Toshiba G9000 Series User Manual
Page 27
G9000 Installation and Operation Manual
17
TABLE 1.5.a Detail of Specifications
Rated Output kVA
80
100
160
225
Rated Output kW
72
90
144
202.5
AC INPUT
Configuration
3 phase, 3 wire
Voltage
480 V +15% to -20%
Frequency
60 Hz +/-10%
Power Factor
>.99 Lagging at 25% - 115% Load
Reflected Current
THD
3% max. at 60% - 100% load (no input filter required)
6% max. at 25% - 59% load.
STATIC BYPASS INPUT
Configuration
3 phase, 3 wire
Voltage
480 V +/-10%
Frequency
60 Hz +/-5%
BATTERY
Type
Lead Acid
Ride Through
Application Specific
Nominal Voltage
480 Vdc
Minimum Voltage
400 Vdc
DC Ripple
0.23%
0.23%
0.23%
0.29%
DC Charging Current
20 Adc
25 Adc
40 Adc
56 Adc
Number of Cells
240
AC OUTPUT
Configuration
3 phase, 3 wire
Voltage
480 V
Voltage Regulation
+/-1%
Frequency
60 Hz
Frequency
Regulation
+/-0.01% in free running mode
Power Factor
0.9 nominal
Power Factor Range
0.9 lagging to 0.95 leading (within output kW rating)
Voltage THD
2% maximum THD at 100% Linear Load
5% maximum THD at 100% non-linear load
Transient Response
+/-2% maximum at 100% load step
+/-1% maximum at loss/return of AC power
+/-5% maximum at load transfer to/from static bypass
Transient Settling
(Recovery) Time
Less than 20ms
Voltage Unbalance
1% maximum at 100% unbalanced load