Specifications – MaxPower Corp Toshiba G9000 Series User Manual
Page 26
16
G9000 Installation and Operation Manual
1.5
SPECIFICATIONS
The UPS nameplate displays the rated kVA as well as nominal voltages and currents. The
nameplate is located on the inside of the UPS front door.
TABLE 1.3 Power Specifications
Rated output
Power
Input voltage
3 phase / 3 wire
Bypass input voltage
3 phase / 3 wire
Output voltage
3 phase / 3 wire
80kVA / 72kW
100kVA / 90 kW
160kVA / 144kW
225kVA / 202.5kW
480V
480V
480V
480V
480V
480V
480V
480V
480V
480V
480V
480V
TABLE 1.4 UPS Module Information
a) Cabinet Dimension
UPS
[kVA]
Width
[in.]
(mm)
Depth
[in.]
(mm)
Height
[in.]
(mm)
Net Weight
[lbs.]
(kg)
Heating
[kBTU/h]
Cable
Knockout
80
27.6
(700)
32.8
(832)
80.6
(2,047)
855
(388)
10.8
BOTTOM
100
27.6
(700)
32.8
(832)
80.6
(2,047)
855
(388)
13.5
BOTTOM
160
35.4
(900)
32.8
(832)
80.6
(2,047)
1,160
(526)
17.8
BOTTOM
225
35.4
(900)
32.8
(832)
80.6
(2,047)
1,230
(558)
25.1
BOTTOM
b) Packing Dimension
UPS
[kVA]
Width
[in.]
(mm)
Depth
[in.]
(mm)
Height
[in.]
(mm)
Gross Weight
[lbs.]
(kg)
80
35.4
(900)
41.3
(1,050)
88.6
(2,250)
990
(450)
100
35.4
(900)
41.3
(1,050)
88.6
(2,250)
990
(450)
160
43.3
(1,100)
41.3
(1,050)
88.6
(2,250)
1,320
(600)
225
43.3
(1,100)
41.3
(1,050)
88.6
(2,250)
1,430
(650)