beautypg.com

MaxPower Corp Toshiba G9000 Series User Manual

Page 49

background image

G9000 Installation and Operation Manual

39

After the completion of the input power cables connection:

With a phase rotation meter, check that the phase rotation of the AC Input power

terminals A, B and C as well as the Bypass Input power terminals A40, B40 and C40

are correct. The proper phase rotation is clockwise A(R)

B(S)

C(T).

3.

Connect the grounding conductor from the input service

entrance to the UPS Ground Bar (E).

4.

Two (2) sources feeding the UPS:

(1) Connect the AC input power cables from the input service entrance to the AC input power

terminals, identified as A, B, C in Figures 3.1 to 3.3. Input cables must be sized for an

ampere rating larger than the maximum input drawn by the converter. (Refer to

equipment nameplate for current ratings.) Confirm that an external bypass input circuit

breaker (MCCB) is installed (refer to WARNING 4, page 1-4). Connect the bypass input

power cables from the input service entrance to the bypass input power terminals,

identified as A40, B40 and C40 in Figures 3.1 to 3.3. Bypass input cables must be sized

for an ampere rating larger than the maximum output current capacity of the UPS. Refer

to Table 3.4 for recommended cable sizes.

(2) Connect the external signal terminal block as desired. Refer to section 2.4 and Figure

2.10 for functional description. 2mm

2

, or less, shielded conductor is recommended.

5.

One (1) source feeding the UPS:

(1) Confirm that an external input circuit breaker sized to protect both the AC input and the

bypass line is installed. (Refer to equipment nameplate for current ratings.) Connect the

bypass input power cables from the input service entrance to the bypass input power

terminals, identified as A40, B40 and C40 in Figures 3.1 to 3.3. Input cables must be

sized for an ampere rating larger than the maximum current capacity of the UPS. Refer to

Table 3.4 for recommended cable sizes.

(2) Using adequately sized conductors and referring to the appropriate figure identified in

Figures 3.1 to 3.3, connect jumper bypass terminals A40, B40, C40 to AC input power

terminals A, B, C as identified in Figures 3.1 to 3.3.

!

NOTE

REQUIRED