beautypg.com

MaxPower Corp Toshiba G9000 Series User Manual

Page 66

background image

56

G9000 Installation and Operation Manual

Note 3

Note 1

Note 2

Code

indication

Status message

Meaning

Guidance

Buzzer

External

relay

contact

Failure

lamp

UF109

DC UNBALANCED

Major unbalance of the neutral point
voltage.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF110

ZERO PHASE
OVERCURRENT

Detection of converter zero-sequence
overcurrent.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF111

UPS CONTROL
CIRCUIT ERROR

Battery current unbalance.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF112

DC CIRCUIT
ABNORMAL

Sudden change of the DC voltage level.

CALL SERVICE
ENGINEER

Continuouss

ound

Major

Lit on

UF119

DC GROUND
FAULT

Detection of DC ground fault UF159
exceeds 10 seconds. UPS transfers to
bypass.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF128

CONTROL
POWER SUPPLY
ABNORMAL

Power supply voltage to IGBT driver PCB
is below the specified level.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF151

DC VOLTAGE
ABNORMAL

24 hours after input power restoration,
batteries does not reach float voltage
level.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker

UF152

DC VOLTAGE
ABNORMAL

Unable to equalize the voltage of various
batteries after 24 hours.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker

UF154

CB2 ABNORMAL

During UVT, status signal from CB2 is
ON.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker

UF156

CHG.STOPPED(B
ATTERY
OVERTEMP.)

UF157 failure persisted for over 2 hours.

CHECK
BATTERY

Intermittent

sound

Minor

Battery

abnormal

Flicker

UF157

BATTERY
OVERTEMPERAT
URE

Detection of overtemperature at the
batteries.

CHECK
BATTERY

Intermittent

sound

Minor

Battery

abnormal

Flicker

UF158

BATTERY LIQUID
LOW

Low level of battery electrolyte solution.

CHECK
BATTERY

Intermittent

sound

Minor

Battery

abnormal

Flicker

UF159

DC GROUND
FAULT

Detection of DC ground fault. Chopper
operation is stopped.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker

UF160

UPS CONTROL
CIRCUIT ERROR

Abnormal behavior of DC current sensor.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker

UF161

CHG.STOPPED(D
C VOLT.
ABNORMAL)

UF151 failure is running for over 24 hours.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker

UF162

BATTERY
ABNORMAL

Failure detection based on battery
self-check.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker

UF163

BATTERY
VOLTAGE
ABNORMAL

Battery voltage is abnormal.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker

UF170

VDB SENSOR
ABNORMAL

Detection of a large variation of the
difference between control-only and
protection-only battery voltage.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker