beautypg.com

MaxPower Corp Toshiba G9000 Series User Manual

Page 68

background image

58

G9000 Installation and Operation Manual

Note 3

Note 1

Note 2

Code

indication

Status message

Meaning

Guidance

Buzzer

External

relay

contact

Failure

lamp

UF301

UPS CONTROL
CIRCUIT ERROR

AD reference has an abnormal value.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF302

UPS CONTROL
CIRCUIT ERROR

Detection of an external interruption
during the software execution.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF303

UPS CONTROL
CIRCUIT ERROR

Timer does not reset in the specified
period (WDT settings)

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF305

UPS CONTROL
CIRCUIT ERROR

Detection of an abnormal clock speed in
the DSP or FPGA.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF306

UPS CONTROL
CIRCUIT ERROR

Control power supply voltage is below the
specified level.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF309

INVERTER
VOLTAGE
ABNORMAL

Inverter voltage is out of the specified
range.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF310

CONTROL
POWER SUPPLY
ABNORMAL

MMS backup control power supplies
exhibit abnormal condition.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF320

UPS CONTROL
CIRCUIT ERROR

Cable disconnection in the parallel
interface board during load supply.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF323

UPS CONTROL
CIRCUIT ERROR

Major communication error during parallel
operation.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF352

CONTROL
POWER SUPPLY
ABNORMAL

SMS backup control power supplies
exhibit abnormal.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker

UF363

UPS CONTROL
CIRCUIT ERROR

Synchronization error signal is being
received for a considerable time.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker

UF371

UPS CONTROL
CIRCUIT ERROR

Minor communication error during parallel
operation.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker

UF372

UPS CONTROL
CIRCUIT ERROR

Unable to synchronize the inverter output
and the bypass voltage when the bypass
is normal.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker

UF374

UPS CONTROL
CIRCUIT ERROR

Cable disconnection in the parallel
interface board.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker

UF375

UPS CONTROL
CIRCUIT ERROR

Unable to achieve synchronization for
parallel operation.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker

UF376

UPS CONTROL
CIRCUIT ERROR

No control response from another UPS
although its detection is possible.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker

UF377

UPS CONTROL
CIRCUIT ERROR

Overload detection signal is being
received continuously for a considerable
time.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker

UF378

UPS CONTROL
CIRCUIT ERROR

No answer for sending synchronizing
signal.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker

UF379

UPS CONTROL
CIRCUIT ERROR

Abnormal clock speed of the parallel
control board processor.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker