18
G9000 Installation and Operation Manual
Phase Displacement
1 deg. maximum at 100% load
Inverter Overload
125% for 2 minutes; 150% for 60 seconds
Crest Factor
2.3
Bypass Overload
1000% for 1 cycle
(with bypass available)
Withstand Rating
65,000 A (with optional fuse)
ENVIRONMENTAL
Cooling
Forced Air
Operating
Temperature
32 F to 104 F ( 0 C to 40 C).
Recommended : 68゚F to 86゚F ( 20 C to 30 C)
Relative Humidity
5%
–
95% Non Condensing
Altitude
0 to 7380 feet No Derating at 40゚C
Location
Indoor (free from corrosive gases and dust)
Paint Color
Munsell N1.5 (Black)
TABLE 1.5.b UPS Efficiencies at Various Loads
UNIT
% Full Load
20%
40%
60%
80%
100%
80 kVA
92.5%
94.3%
95.0%
95.2%
95.8%
100 kVA
92.5%
94.3%
95.0%
95.2%
95.8%
160 kVA
94.7%
95.7%
96.2%
96.5%
96.5%
225 kVA
94.9%
96.2%
96.5%
96.5%
96.5%