G9000 Installation and Operation Manual
57
Note 3
Note 1
Note 2
Code
indication
Status message
Meaning
Guidance
Buzzer
External
relay
contact
Failure
lamp
UF201
INVERTER
OVERVOLTAGE
Detection of output overvoltage.
CALL SERVICE
ENGINEER
Continuous
sound
Major
Lit on
UF202
INVERTER
UNDERVOLTAGE
Output voltage dropped.below specs.
CALL SERVICE
ENGINEER
Continuous
sound
Major
Lit on
UF203
INVERTER
OVERCURRENT
Detection of inverter overcurrent.
CALL SERVICE
ENGINEER
Continuous
sound
Major
Lit on
UF204
OUTPUT CIRCUIT
ABNORMAL
Detection of a large variation of the
reference error signal (current reference
and actual current).
CALL SERVICE
ENGINEER
Continuous
sound
Major
Lit on
UF206
UPS CONTROL
CIRCUIT ERROR
Discrepancy between output voltage and
external voltage (bypass, common ac bus)
CALL SERVICE
ENGINEER
Continuous
sound
Major
Lit on
UF207
ZERO PHASE
OVERCURRENT
Inverter zero-sequence overcurrent.
CALL SERVICE
ENGINEER
Continuous
sound
Major
Lit on
UF208
UPS CONTROL
CIRCUIT ERROR
Cross current is abnormal.
CALL SERVICE
ENGINEER
Continuous
sound
Major
Lit on
UF209
52C ABNORMAL
Error to close the contactor 52C.
CALL SERVICE
ENGINEER
Continuous
sound
Major
Lit on
UF210
52C ABNORMAL
Error to open the contactor 52C.
CALL SERVICE
ENGINEER
Continuous
sound
Major
Lit on
UF211
52C ABNORMAL
No answer from contactor 52C during
inverter operation.
CALL SERVICE
ENGINEER
Continuous
sound
Major
Lit on
UF213
OVERTEMP
Heatsinks temperature exceeds thermal
settings.
CALL SERVICE
ENGINEER
Continuous
sound
Major
Lit on
UF214
COOLING FAN
ABNORMAL
Thermal relay activated protection.
CALL SERVICE
ENGINEER
Continuous
sound
Major
Lit on
UF217
INVERTER
OVERVOLTAGE
Detection of inverter output phase
overvoltage.
CALL SERVICE
ENGINEER
Continuous
sound
Major
Lit on
UF230
ZERO PHASE
OVERCURRENT
Detection of zero-sequence overcurrent.
CALL SERVICE
ENGINEER
Continuous
sound
Major
Lit on
UF253
UPS CONTROL
CIRCUIT ERROR
Discrepancy between output voltage and
inverter voltage, or between output
voltage and bypass voltage.
CALL SERVICE
ENGINEER
Intermittent
sound
Minor
Flicker
UF256
OUTPUT
VOLTAGE
ABNORMAL
Output voltage is outside of the specified
range.
CALL SERVICE
ENGINEER
Intermittent
sound
Minor
Flicker
UF257
52C ABNORMAL
Contactor 52C failed to open during load
transfer from inverter to bypass.
CALL SERVICE
ENGINEER
Intermittent
sound
Minor
Flicker
UF258
LOAD ABNORMAL
Load transfer due to overload for over 4
times within 5 minutes.
CALL SERVICE
ENGINEER
Intermittent
sound
Minor
Flicker
UF259
ANOTHER UPS
ABNORMAL
No detection of another UPS voltage
signal.
CALL SERVICE
ENGINEER
Intermittent
sound
Minor
Flicker