MaxPower Corp Toshiba G9000 Series User Manual

Page 42

background image

32

G9000 Installation and Operation Manual

Details of input contacts for remote access : TN2

Terminals 7 to 8

Remote "Inverter Start" input terminal (IN1)

Used to start inverter from a remote location. UPS must be programmed for remote

operation. Refer to Operations Menu for procedure.

Terminals 9 to 10

Remote "Inverter Stop" input terminal (IN2)

Used to stop inverter from a remote location. UPS must be programmed for remote

operation. Refer to Operations Menu for procedure.

Terminals 11 to 12 "Battery Temp. High" contact input (IN3)

Input fed by a thermocouple that monitors battery temperature. The converter float

voltage level is reduced for battery over-temperature conditions. External

thermocouple is user supplied

Terminals 13 to 14

"Power Demand” Command contact input (IN4)

This contact is used to control the input power. Power demand is turned ON when

the contact is closed, and power demand is turned OFF when the contact is open.

Terminals 15 to 16 "Remote EPO" contact input

Used to perform a remote UPS Emergency Power Off (EPO).

The load will be dropped.

The UPS is equipped with a selectable input contact item.

The above items are the default settings.

Contact Toshiba International Corporation for setup information.

In all cases, a switch having a protective cover is recommended in order to reduce

the possibility of accidental operation.

!

NOTE

CAUTION