Gate opens using transmitter, but will not close using transmitter (Low Current Receiver only)

STEP 1 The problem is most likely the programming of the Low Current Receiver (P2 relay is programmed

to latch mode)

STEP 2 On the Patriot control board locate press and hold the “LED Indicator” pushbutton.

STEP 3 Look in the lower left corner of the Patriot control board and note any LED’s that are on.

STEP 4 If the “OPEN INPUT” is on then the receiver (P2) is programmed to latch mode.

STEP 5 Go to page 21 “Resetting receiver P2 relay to momentary mode”

STEP 6 If this does not correct the problem return to troubleshooting section 4 and perform steps 1-6.

STEP 7 If problem is not corrected; call the factory for further troubleshooting.

13.

Gate only operates when the “LED INDICATOR” is pressed.

STEP 1 An accessory wiring problem or a bad control board can cause this. This problem can be intermittent

and will take a little patience in locating the problem.

STEP 2 Verify that the problem exists when using the “Open /Close Command” on the control board. Press

the “Open/Close Command” push button and verify gate will not operate.

STEP 3 Press the “Led Indicator” on the control board and hold then press the “Open/Close Command” push

button on the control board. If the gate operates, proceed to step 4.

STEP 4 Remove the J2 accessory-wiring plug from the control board. This connector can be disconnected

from the control board by placing a finger under the plug and pulling to remove.

STEP 5 Press the “Open/Close Command” push button and verify gate operation. If gate operates then

reconnect the J2 connector and verify gate operation using the “Open/Close Command” push button.
If gate fails to operate when the J2 connector is reconnected then the problem is most likely in the
accessory wiring. Most likely there is a bad ground connection on the accessory. Verify all wiring on
the accessories connected to the J2 connector.

STEP 6 If gate fails to operate when the J2 connector is disconnected, then the control board is most likely the

problem. Please contact the factory for further troubleshooting options.

NOTE: Keep in mind that this is an intermittent problem and it might be necessary to try this a few times to

verify the problem.

NOTE: If you have a DC volt meter, check the following. Set the gate to the fully open or close position and

verify that an open or close limit LED is on when the led indicator is pressed. Take voltage reading
on the following J2 connector terminals. Pin 3,4,5,6,8,9,10,11,12. The reading should be 5 vdc. A
reading of approximately 2 or 3 vdc indicates a problem. Call the factory for corrective action. This
could indicate a bad LED on the corresponding J2 connector pin which can be resolved by removing
the LED light from the control board.

14.

Oracle Remote/Transmitter will not operate the gate

STEP 1 Press and hold the LED indicator on the control board

STEP 2 Press the Remote/Transmitter button to operate the gate, the push button input LED on the control

board should light. If it does not verify wiring from DFGCU receiver to J5 is not damaged.

STEP 3 If wiring checked good, verify batteries in remote/transmitter are good. Replace battery if necessary.

STEP 4 If problem persist refer to page 19 and try “Learning remote/transmitter” again.

STEP 5 If relearning the remote/transmitter to DFGCU receiver does not correct problem, call factory for