PROFIBUS DP start-up
Typ 8750
PDI: Process Data Input (from the process controller to the controller)
name
description
identifier
PDI:POS
Actual position (position)
Actual value of positioner as ‰.
Value range 0 – 1000.
Values < 0 or > 1000 are
possible if e.g.
X.TUNE has not
run through correctly.
GSD file:
PDI:POS
Identifier (HEX):
41, 40, 00
PDI:CMD
Set-point position (command)
Set-point value of positioner
as ‰.
Value range 0 – 1000.
GSD file:
PDI:CMD
Identifier (HEX):
41, 40, 01
PDI:PV
Process actual value
(process value)
Actual value of process controller
in physical unit (as set in the menu
P.CO INP or P.CO SCAL),
max. value range -999 – 9999,
depending on internal scaling.
GSD file:
PDI:PV
Identifier (HEX):
41, 40, 02
PDI:SP
Process set-point value (set-point)
Set-point value of process
controller in physical unit
(as set in the menu
P.CO INP or
P.CO SCAL),
max. value range -999 – 9999,
depending on internal scaling.
GSD file:
PDI:SP
Identifier (HEX):
41, 40, 03
name
description
identifier
PDI:TEMP Device temperature (temperature)
Temperature of 0.1 °C is
measured on the CPU board by
the sensor,
value range -550 (-55 °C) –
+1250 (+125 °C).
GSD file:
PDI:TEMP
Identifier (HEX):
41, 40, 04
PDI:MODE Operating state (operation mode)
Operating state:
0:
AUTO
1:
MANUAL
2:
XTUNE
9:
P.QLIN
10:
P.TUNE
12:
BUSSAFEPOS
GSD file:
PDI:MODE
Identifier (HEX):
41, 00, 05
PDI:ERR
Error
Indicates the number of the
process value (output) which was
not written. The value is retained
until it is deleted with
PDO:ERR.
HEX
14
PDO:CMD / SP
16
PDO:MODE
GSD file:
PDI: ERR
Identifier (HEX):
41, 00, 06