Operationandfunction

Type 8006, 8702

function

Description

Close valve
completely active

The close valve completely function is
activated.

Open valve
completely active

The open valve completely function is
activated.

Defective power
requirement

The power requirement of the device is
monitored. If this value is outside defined
limits, this function is actuated. An excessively
high or low power requirement may indicate a
defective device.

Defective internal
power supply

The operating voltage of the device is
monitored. If the defined limits exceed the
maximum or drop below the minimum, this
function is actuated.

Defective power
supply to the
sensor

The power supply voltage to the sensor is
monitored. If the defined limits exceed the
maximum or drop below the minimum, this
function is actuated.

Defective data
storage

If data storage is in the non-volatile memory of
the device, a fault has occurred.

Sensor fault

The device is able to detect a defective
sensor via a self-test.
If this is the case, this function is activated.

MFI fault

The field bus module (MFI) is defective
or incorrectly equipped. Field bus
communication is not possible.

x Limit

The measured value has exceeded or dropped
below a limit value which can be configured.

function

Description

w Limit

The set-point value has exceeded or dropped
below a limit value which can be configured.

y2 Limit

The actuating variable has exceeded or
dropped below a limit value which can be
configured.

Totalizer Limit

The totalizer has exceeded or dropped below
a limit value which can be configured.

Tab. 4 : Relay output signals possible functions