Conditions of use – Burkert Type 8712 User Manual
Page 12
12
Technicaldata
Type 8006, 8702
8006 35.0 Nm3/h
Made in France
00182381
W49MM
24V DC 13W DP
CH4
S/N 1004
FKM
Type of the
device
Nominal flow rate
(Q
nom
) and unit
Operating medium
Material of the seal
Supply voltage
Max. power consumed
Output signal
Construction
code
Item no. of the
device
Serial
number
Fig. 3: Details of a name plate
Calibration data
00202378
Medium 1
P1: 0.700 barg
Mounting: Horizontal mounting
QC passed: 25.11.2011
Calibration date
Calibration
pressure
Mounting
position
Item no. of the
device
Calibration fluid
Fig. 4: Details of a calibration plate
6.2.
conditions of use
Warning
risk of injury from malfunction due to effects of the weather!
The MFM / MFC is not designed for unrestricted use outdoors.
• Protect the device from direct sunlight.
• Observe the ambient temperature range of the device.
• Protect the device from humidity.
setting
value
Ambient temperature
Types 8702 / 8712: -10 °C to +50 °C
Types 8006 / 8626: -10 °C to +45 °C
For UL devices: 0 °C to 40 °C
Medium temperature
for oxygen: -10 °C to +60 °C
for other fluids: -10 °C to +70 °C
Air humidity
< 95%, without condensation
Relative humidity for UL
devices
80% up to a temperature of 31°C,
with a linear decrease to a relative
humidity of 50% at 40°C
Protection class
according to EN 60529
Only if devices are cabled and the
connectors are plugged in and
tightened: IP65
Absolute height above
sea level for UL devices
2000 m max.
Operating environment
Indoors, with pollution degree 2
English