Profibus user manual – BEI Sensors PHU9 Absolute Hollow Shaft Encoder User Manual
Page 27

PROFIBUS USER MANUAL
Preliminary
27
BEI IDEACOD SAS
Espace Européen de l’Entreprise
9, rue de Copenhague
B.P. 70044 Schiltigheim
F 67013 Strasbourg Cedex
Tél
: +33 (0)3 88 20 80 80
Fax : +33 (0)3 88 20 87 87
Mail :
Web : www.bei-ideacod.com
6.2 Supported diagnostic messages
In the following the different diagnostic
messages are described in detail.
6.2.1 Extended diagnostics header
Byte 7 contains the length of the extended
diagnostics (including header itself).
6.2.2 Operating status
Diagnostic byte 9 contains certain parameters
(set in the system configuration).
Bit Definition
0
1
0
Direction of rotation CW
CC
W
1
Class 2 functionality
Off
On
2
Diagnostic routine
Off
On
3
Scaling function
Off
On
6.2.3 Encoder type
Diagnostic byte 10 contains the encoder
version (singleturn or multiturn).
Byte 10
Definition
0
Singleturn encoder
1
Multiturn encoder
6.2.4 Singleturn resolution
Diagnostic bytes 11-14 contain the real
(physical) resolution per revolution of the
encoder.
6.2.5 Number of revolutions
Diagnostic bytes 15 and 16 contain the real
(physical) number of revolutions of the
encoder. Standard values are 1 for singeturn
and 65535 for multiturn devices.
6.2.6 Profile version
Diagnostic bytes 24 and 25 contain the profile
version of the encoder.
Byte
24
25
Bit
15 – 8
7 – 0
Data
2
7
- 2
0
2
7
- 2
0
Revision No.
Index
6.2.7 Software version
Diagnostic bytes 26 and 27 contain the
software version of the encoder.
Octet 26
27
Bit
15 – 8
7 - 0
Data
2
7
to 2
0
2
7
to 2
0
Revision No. Index
6.2.8 Operating time
The operating time of the encoder is not
supported set to FFFFFFFF hex
6.2.9 Zero offset
The zero offset is output in diagnostic bytes 32
to 35.
6.2.10 Programmed resolution
The programmed resolution per revolution is
output in diagnostic bytes 40 to 43. The value is
only valid if the scaling factor is based on the
parameter „resolution per revolution“ (cp.
5.1.3).
6.2.11 Programmed total resolution
The programmed, respectively calculated
total resolution is output in diagnostic bytes 44-
47.
6.2.12 Serial number
Diagnostic bytes 48-57 are intended for a serial
number.