Franklin Fueling Systems T5 Series Fuel Management System Operators Guide User Manual
Page 40
36
From the National Work Group on Leak Detection (NWGLDE) web site. 20 Feb. 2007.
Comments
Not evaluated using manifolded tank systems. Therefore, this certification is only applicable
when there is a probe used in each tank and the siphon is broken during testing.
Tests only portion of tank containing product.
As product level is lowered, leak rate in a leaking tank decreases (due to lower head
pressure). Consistent testing at low levels could allow a leak to remain undetected.
EPA leak detection regulations require testing of the portion of the tank system which
routinely contains product.
TS-1000 and TS-1001 can support up to 4 tanks.
TS-2001 can support up to 8 tanks.
TS-5 can support up to 12 tanks.
TS-608 can support up to 8 tanks.
TS-550 and TS-5000 can support up to 72 tanks.
TS-750 can support up to 4 tanks, but does not provide fuel logistics, remote monitoring and
other business management options available with TS-1000, TS-1001 and TS-2001.
Franklin Fueling Systems
Evaluator: Ken Wilcox Associates
3760 Marsh Road.
Tel: (816) 443-2494
Madison, WI 53718
Dates of Evaluation: 08/05/92, 09/05/97,
05/14/98, 08/21/02, 01/18/06
Tel: (800) 225-9787
E-mail: [email protected]
URL: www.franklinfueling.com
|
Home
|
Vendors: A - F
|
Vendors: G - M
|
Vendors: N - S
|
Vendors: T - Z
|
Method Index
|
Glossary
|
Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the
performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations. For full details, please refer to
our expanded "
DISCLAIMER
" page.
Page 2 of 2
Franklin Fueling Systems C
2/21/2007
http://www.nwglde.org/evals/franklin_fueling_c.html