Special Product Alarms

Displayed Alarm

Description

Recommended Actions

Reference Source

Alpha Volume

Correction Error

These Alarms refer to temperature 

correction coefficients used by the 

console to calculate Net Volume. When 

these values are entered too high or 

too low, an alarm condition will occur.

Verify that the Volume in the Correction 

Type matches the specifications of 

the product used in ‘Special Products’ 

Programming. These values should be 

listed in the product manufacturer’s Spec 

Sheets.

Special Products in

Programming Manual** 

/ Applicable Product 

Literature***

API Volume

Correction Error

These Alarms refer to temperature 

correction coefficients used by the 

console to calculate Net Volume. When 

these values are entered too high or 

too low, an alarm condition will occur.

Verify that the Volume in the Correction 

Type matches the specifications of 

the product used in ‘Special Products’ 

Programming. These values should be 

listed in the product manufacturer’s Spec 

Sheets.

Special Products in

Programming Manual** 

/ Applicable Product 

Literature***

Level Error

The level of the product float on 

the probe listed with the alarm has 

exceeded a possible level according to 

the programming.

Verify that the following parameters are 

programmed correctly according to site 

specifications: Correction Table, Gradient, 

Probe Type, and Product Offset.

Probes Setup in

Programming Manual** 

/ Applicable Equipment 

Guide*

Net Error

The net volume of the product float 

on the probe listed with the alarm has 

exceeded a possible volume according 

to the programming; related to Volume 

Correction.

Verify that the following parameters are 

programmed correctly according to site 

specifications: Correction Table, Gradient, 

Probe Type, and Product Offset.

Special Products in

Programming Manual** 

/ Applicable Product 

Literature***

Product Volume

Error

The volume of the product float on 

the probe listed with the alarm has 

exceeded a possible volume according 

to the programming.

Verify that the following parameters are 

programmed correctly according to site 

specifications: Correction Table, Gradient, 

Probe Type, and Product Offset.

Probes Setup in

Programming Manual** 

/ Applicable Equipment 

Guide*

Ullage Error

The Ullage level on the tank/manifold 

listed with the alarm has exceeded 

a possible level according to the 

programming.

Verify that the following parameters are 

programmed correctly according to site 

specifications: Correction Table, Gradient, 

Probe Type, and Product Offset.

Special Products in

Programming Manual** 

/ Applicable Product 

Literature***

Water Volume

Error

The Water Volume on the tank/

manifold listed with the alarm has 

exceeded a possible level according to 

the programming.

Verify that the following parameters are 

programmed correctly according to site 

specifications: Correction Table, Gradient, 

Probe Type, and Product Offset.

Special Products in

Programming Manual**/ 

Applicable Product 

Literature***

* Bulletins and Equipment Guides can be found on INCON’s web site - http://www.incon.com
** The T5 Series Installation Guide (p/n 000-2150) and the T5 Series Programming Manual (000-2142) can be found on INCON’s 

web site - http://www.incon.com 

*** If the tank is not listed as a standard tank in Appendix A: Standard Tanks Table (in the T5 Series Programming Manual (p/n 000-

2142), use the tank chart from the manufacturer to create a custom correction table.