Franklin Fueling Systems T5 Series Fuel Management System Operators Guide User Manual
Page 37
33
FMS
Special Product Alarms
Displayed Alarm
Description
Recommended Actions
Reference Source
Alpha Volume
Correction Error
These Alarms refer to temperature
correction coefficients used by the
console to calculate Net Volume. When
these values are entered too high or
too low, an alarm condition will occur.
Verify that the Volume in the Correction
Type matches the specifications of
the product used in ‘Special Products’
Programming. These values should be
listed in the product manufacturer’s Spec
Sheets.
Special Products in
Programming Manual**
/ Applicable Product
Literature***
API Volume
Correction Error
These Alarms refer to temperature
correction coefficients used by the
console to calculate Net Volume. When
these values are entered too high or
too low, an alarm condition will occur.
Verify that the Volume in the Correction
Type matches the specifications of
the product used in ‘Special Products’
Programming. These values should be
listed in the product manufacturer’s Spec
Sheets.
Special Products in
Programming Manual**
/ Applicable Product
Literature***
Level Error
The level of the product float on
the probe listed with the alarm has
exceeded a possible level according to
the programming.
Verify that the following parameters are
programmed correctly according to site
specifications: Correction Table, Gradient,
Probe Type, and Product Offset.
Probes Setup in
Programming Manual**
/ Applicable Equipment
Guide*
Net Error
The net volume of the product float
on the probe listed with the alarm has
exceeded a possible volume according
to the programming; related to Volume
Correction.
Verify that the following parameters are
programmed correctly according to site
specifications: Correction Table, Gradient,
Probe Type, and Product Offset.
Special Products in
Programming Manual**
/ Applicable Product
Literature***
Product Volume
Error
The volume of the product float on
the probe listed with the alarm has
exceeded a possible volume according
to the programming.
Verify that the following parameters are
programmed correctly according to site
specifications: Correction Table, Gradient,
Probe Type, and Product Offset.
Probes Setup in
Programming Manual**
/ Applicable Equipment
Guide*
Ullage Error
The Ullage level on the tank/manifold
listed with the alarm has exceeded
a possible level according to the
programming.
Verify that the following parameters are
programmed correctly according to site
specifications: Correction Table, Gradient,
Probe Type, and Product Offset.
Special Products in
Programming Manual**
/ Applicable Product
Literature***
Water Volume
Error
The Water Volume on the tank/
manifold listed with the alarm has
exceeded a possible level according to
the programming.
Verify that the following parameters are
programmed correctly according to site
specifications: Correction Table, Gradient,
Probe Type, and Product Offset.
Special Products in
Programming Manual**/
Applicable Product
Literature***
* Bulletins and Equipment Guides can be found on INCON’s web site - http://www.incon.com
** The T5 Series Installation Guide (p/n 000-2150) and the T5 Series Programming Manual (000-2142) can be found on INCON’s
web site - http://www.incon.com
*** If the tank is not listed as a standard tank in Appendix A: Standard Tanks Table (in the T5 Series Programming Manual (p/n 000-
2142), use the tank chart from the manufacturer to create a custom correction table.