29

System

Displayed Warning

Description

Recommended Actions

Reference Source

IS Barrier Violation

The system has received an indication 

that there is a Non-Intrinsically Safe 

module installed in the IS area or that 

the IS barrier has been removed.

Visually verify that all modules are 

installed on the correct side of the IS 

Barrier.

Installation Guide** / 

Applicable Bulletins*

Low Battery

Backup Battery should be replaced.

Replace the backup battery with an exact 

replacement from INCON.

Installation Guide** / 

Applicable Bulletins*

Modem Error

The number of expected Modem 

Modules does not equal the number of 

Modem Modules installed.

Verify the physical number of Modem 

Modules installed and compare with the 

number of Modem ‘Modules Expected’ in 

the programming.

General Setup in

Programming Manual**

 / Applicable Bulletins*

Power Supply Module

is Offline

This warning is only possible if there 

is a TS-EXPC expansion console 

connected. Failure to recognize the 

expansion console’s PSM.

Cycle power to the console. Visually verify 

that the green ‘RUN’ light on the module 

is on continuously after the system boot is 

complete.

Installation Guide** / 

Applicable Bulletins*

Printer Paper Jam

Paper feed error. Paper or debris is 

stuck in the printer.

Visually inspect the printer for the 

problem. Correctly route the paper through 

the printer to clear this warning.

Installation Guide** / 

Applicable Bulletins*

Probe Module

is Offline

The specified Probe Module listed with 

the alarm has experienced a problem 

or may not be recognized by the 

Controller Module.

Cycle power to the console. Visually 

verify that the green ‘RUN’ light on 

the applicable Probe Module is on 

continuously after the system boot is 

complete.

Installation Guide** / 

Applicable Bulletins*

Probe Module

Number Mismatch

The number of expected Probe 

Modules does not equal the number of 

Probe Modules installed.

Verify the physical number of Probe 

Modules installed and compare with the 

number of Probe ‘Modules Expected’ in 

the programming.

General Setup in

Programming Manual**

 / Applicable Bulletins*

Relay Module

Number Mismatch

The number of expected Relay 

Modules does not equal the number of 

Relay Modules installed. 

Cycle power to the console. Visually 

verify that the green ‘RUN’ light on 

the applicable Relay Module is on 

continuously after the system boot is 

complete.

Installation Guide** / 

Applicable Bulletins*

Relay Module

is Offline

The specified Relay Module listed with 

the alarm has experienced a problem 

or may not be recognized by the 

Controller Module.

Verify the physical number of Relay 

Modules installed and compare with the 

number of Relay ‘Modules Expected’ in 

the programming.

General Setup in

Programming Manual**

 / Applicable Bulletins*

Relay Module

Setup Error

This alarm is an indication that all 

channels have been enabled. With all 

six (6) 2A relay channels in use, 10A 

channels seven (7) and eight (8) may 

not be enabled. 

Verify Relay Module programming.

Module Setup in

Programming Manual**

* Bulletins and Equipment Guides can be found on INCON’s web site - http://www.incon.com
** The T5 Series Installation Guide (p/n 000-2150) and the T5 Series Programming Manual (000-2142) can be found on INCON’s web 

site - http://www.incon.com