MLC 104 Series MediaLink Controllers • Hardware Setup

Hardware Setup, cont’d

2-4

MLC 104 Series MediaLink Controllers • Hardware Setup

2-5

d

MLS RS-232 port — This port can control an optional Extron

switcher or other RS-232 controllable device.

If you connect an optional switcher (such as an Extron

MLS Series switcher) to the MLC, you must connect a ground

wire between the switcher and the MLC, as shown in the

following diagram.

MLC/IR

A B C

MediaLink
Switcher's
rear panel
MLC/IR port

NOTE

You must connect a

ground wire

between the MLC

and MLS.

RS-232

MLS

A B

Rx

Tx

GR

OUND

Ground ( )

Transmit (Tx)

B

Receive (Rx)

A

Transmit (Tx)

Receive (Rx)

B
A

MLC 104 Series

Right Side Panel

N

For a list of Extron switchers this connector supports, refer

to the

MLC 104 Series User's Manual.

e

PWR (power) connector — To provide power to the MLC,

connect a cable between this port and a 12 VDC, 1 amp

(maximum) power supply, as shown below. For power wiring

instructions, see the diagram on the following page.

Connecting an MLC 104 Series controller

to an external power supply

MLC 104 Series

Right Side Panel

12V

PWR

GR

OUN

D

+12V IN

Ground ( )

+12 VDC input

Ground all devices.

An external

power supply

(12 VDC, 1 A max.)

N

Power the controller via an external power supply, not

from an Extron switcher. The controller requires a separate

12 VDC power supply.

N

Check the power supply’s polarity before connecting it to

the MLC. See the diagram below.

Power Supply
Output

Cord

Ridges

Smooth

A

A

0.2” (5 mm) MAX.

MLC's
Power
Port

12V

PWR

GR

OUND

+12V IN

SECTION A–A

Power wiring

f

LAN connector and LEDs (IP model only)

— An Ethernet

connection can be used on an ongoing basis to control the

MLC 104 IP (and the devices connected to it) in an Ethernet

network.

Use a straight-through cable for connection to a switch,

hub, or router.
Use a crossover cable for connection directly to a PC.

Configure the settings for this port via either SIS commands, an

embedded Web page, or Global Configurator.
LAN port defaults are as follows:
IP address: 192.168.254.254

gateway IP address: 0.0.0.0

subnet mask: 255.255.0.0

DHCP: off