5-2 SDI-12 Command and Response Protocol
H-3531
5.1 Measure Command
The Measure Command causes a new measurement sequence to be executed. Data values
generated in response to this command are stored in the sensor's buffer for subsequent collection
using "D" commands. The data will be retained in the sensor until another "M", " C", or "V"
command is executed.
Command
Response
Description
"aM!"
"atttn
Initiate measurement
"aM1!"
"atttn
Initiate measurement
Where:
a
is the sensor address ("0-9", "A-Z", "a-z", "*", "?").
M
is an upper-case ASCII character
ttt
is a three digit integer (000-999) specifying the maximum time, in seconds,
the sensor will take to complete the command and have measurement data
available in its buffer.
n
is a single digit integer (0-9) specifying the number of values that will be
placed in the data buffer. If "n" is zero (0), no data will be available using
subsequent "D" commands.
Upon completion of the measurement, a service request "a
indicating the sensor data is ready. The data recorder may wake the sensor with a break and
collect the data any time after the service request is received or the specified processing time has
elapsed.
Example of a H-3531 "aM!" command:
Command
Response
Time
Values
Description
"aM!"
"a0064
6 sec
4
Make measurement
Subsequent Command
Response
"aD0"
a+AA.AA+BB.BBBB+CC.C+DD.D
Where:
AA.AA
= Stage (feet, inches, meters etc.)
BB.BBBB
= Pressure (PSI)
CC.C
= Temperature (C)
DD.D
= Power Supply Voltage (Volts)